NORD USS and Modbus RTU Manual
54 Subject to technical amendments BU 0050 GB-3111
Setting value / Description / Note
Bus – Actual value 1
(Bus – Actual value 1)
The return value 1 (IW1) can be set for bus control in this parameter.
SK 300E, SK 700E SK 750E
0 = Off
1 = Actual frequency
2 = Actual speed
3 = Current
4 = Torque current
5 = Status of digital inputs and relay
6 = Actual position (only POSICON,
SK700/750E)
7 = Setpoint position (only POSICON,
SK700/750E)
8 = Setpoint frequency
9 = Error number
10 = Actual position increment
1
(only
POSICON, SK700/750E)
11 = Setpoint position increment
1
(only
POSICON, SK700/750E)
12 = BUS I/O Out Bits 0-7
SK 500E
0 = Off
1 = Actual frequency
2 = Actual speed
3 = Current
4 = Torque current (100% = P112)
5 = State of digital inputs and outputs
2
6 = Actual position Low word
7 = Setpoint position Low word
8 = Setpoint frequency
9 = Error number
10 = Actual position increment Low word
11 = Setpoint position increment Low word
12 = Bus I/O Out Bits 0...7
13 = Actual position High word
14 = Setpoint position High word
15 = Actual position increment High word
16 = Setpoint position increment High word
17 = Value analog input 1 (P400)
18 = Value analog input 2 (P405)
19 = Setpoint frequency master value (P503)
20 = Setpoint frequency after master value ramp
21 = Actual frequency without master value slip
22 = Speed from encoder
(only possible with SK 52x/53xE and
encoder feedback)
23 = Actual frequency with slip, "Actual frequency
with slip"
24 = Master value, actual freq. with slip, "Master
value, actual freq. with slip"
NOTE: For SK 540 and SK545E 5 actual values are available. These are all set in
parameter P543, which is divided into 5 array elements for this purpose.
Parameters P544 and P545 are not required for this inverter version.
[-01] = Actual bus value 1
[-02] = Actual bus value 2
[-03] = Actual bus value 3
[-04] = Actual bus value 4
[-05] = Actual bus value 5
Actual bus value 2
(Actual bus value 2)
The return value 2 (IW2) can be set for bus control in this parameter.
For setting values, see parameter (P543)
Actual bus value 3
(Actual bus value 3)
In this parameter, the return value 3 (IW3) can be set for bus control. This is only available if P546
3 (only applies for SK 700E / SK 750E).
For setting values, see parameter (P543)
An indicated revolution of the motor results from 8192 encoder increments.
The assignment of the digital inputs in P543/ 544/ 545 = 5
Bit 0 = DigIn 1 Bit 1 = DigIn 2 Bit 2 = DigIn 3 Bit 3 = DigIn 4
Bit 4 = DigIn 5 Bit 5 = DigIn 6 Bit 6 = DigIn 7 Bit 7 = Reserved
Bit 8 = Reserved Bit 9 = Reserved Bit 10 = Reserved Bit 11 = Reserved
Bit 12 = Out 1 Bit 13 = Out 2 Bit 14 = Out 3 Bit 15 = Out 4