1.8 USS Frequency inverter settings
BU 0050 GB-3111 Subject to technical amendments 55
Parameter
Setting value / Description / Note
Comments
P546 (P)
Function Bus setpoint 1
(Function of bus setpoint 1)
0 ... 7 (47)
{ 1 }
In this parameter, a function is assigned to the delivered setpoint 1 (SW1) for bus control.
NOTE: Further details can be found in the respective FI manual or in the description of P400.
SK 300E, SK 700E SK 750E
0 = Off
1 = Setpoint frequency (16 bit)
2 = 16 Bit setpoint position
(only POSICON SK700/750E)
3 = 32 Bit setpoint position
(only POSICON, SK700/750E and if
PPO- type 2 or 4 are selected)
4 = Control terminals POSICON (only
POSICON, SK700/750E, 16Bit)
5 = Setpoint position (16 Bit) increment
1
(onlyPOSICON, SK700/750E)
6 = Setpoint position (32 Bit) increment
1
(onlyPOSICON, SK700/750E)
7 = Bus IO In Bits 0-7
SK 500E
0 = Off
1 = Setpoint frequency (16 bit)
2 = Torque current limit (P112)
3 = Actual frequency PID
4 = Frequency addition
5 = Frequency subtraction
6 = Current limit (P536)
7 = Maximum frequency (P105)
8 = Actual PID frequency limited
9 = Actual PID frequency monitored
10 = Torque servo mode (P300)
11 = Lead torque (P214)
12 = Reserved
13 = Multiplication
14 = PI process controller actual value
15 = PI process controller setpoint
16 = PI process controller lead
17 = Digital In bits 0...7
18 = Reserved
19 = Set relay (P434/441/450/455=38)
20 = Set analog output (P418=31)
21 = Setpoint position Low word
(SK 530E and above)
22 = Setpoint position High word
(SK 530E and above)
23 = Setpoint position increment Low word
(SK 530E and above)
24 = Setpoint position increment High word
(SK 530E and above)
25 = ... 45 reserved
46 = Setpoint torque process controller
47 = Gearing transfer factor
NOTE: For SK 540 and SK545E 5 setpoints are available. These are all set in parameter
P546, which is divided into 5 array elements for this purpose. Parameters P547
and P548 are not required for this inverter version.
[-01] = Bus setpoint 1
[-02] = Bus setpoint 2
[-03] = Bus setpoint 3
[-04] = Bus setpoint 4
[-05] = Bus setpoint 5
P547 (P)
Function Bus setpoint 2
(Function of bus setpoint 2)
except SK 54xE
0 ... 46 (47)
{ 0 }
In this parameter, a function is assigned to the delivered setpoint 2 (SW2) for bus control.
0 = Off
1 = Setpoint frequency
2 = Torque current limit (P112)
3 = Actual frequency PID
4 = Frequency addition
5 = Frequency subtraction
6 = Current limit (not SK 300E)
7 = Maximum frequency (not SK 300E)
8 = Actual PID frequency limited
9 = Actual PID frequency monitored
10 = Torque (not SK 300E)
11 = Torque lead (not SK 300E)
12 = Control terminals POSICON (not
SK 300E)
13 = Multiplication (not SK 300E)
14 = PI process controller actual value
15 = PI process controller setpoint
16 = PI process controller lead
17 = Digital In bits 0...7
18 = Curve travel calculator (not SK 300E)
19 = Set relay
20 = Set analog output
21 = Setpoint position Low word
(SK 530E and above)
22 = Setpoint position High word
(SK 530E and above)
23 = Setpoint position increment Low word
(SK 530E and above)
24 = Setpoint position increment High word
(SK 530E and above)
25 = ... 45 reserved
46 = Setpoint, torque process controller
(not SK 300E)
47 = Gearing transfer factor (only SK 500E)