EasyManua.ls Logo

Nordson iControl - Installation Guide; Installation Introduction; CAN Network Connections Setup

Nordson iControl
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
iControlr PROFIBUSr, PROFINETr, DeviceNett, and EtherNet/IPt Generation 4 Slot 9 Gateway
19
Part 160593002
E 2020 Nordson Corporation
Write all bytes of the
IO Module
Done
Done
Set the “Wait”
byte to Zero
Write Data to
remaining bytes
of IO Module
Set the”Wait”
byte to a
non-zero value
Scan 1
Scan 2
Scan 3
Scan 1
Single Scan Method
Multiple Scan Method
Figure 6 Sending Messages
Broadcast Messages from the PLC (Module 1)
Table 5 Commonly Used Broadcast Messages from PLC (IO Module 1)
Message No. at
Address Offset 0
Description No. of
Data Bytes
Range of Data Values
(Address Offsets 1 thru 8)
Notes
1 Trigger Guns 8 Each bit is mapped to a gun A
2 Lockout All Guns 1 Lockout=1 (in Data Byte #1)
3 Disabled Alarm Outputs 1 Alarms Disabled=1 (in Data Byte #1)
6 Reset All Alarms/Faults 8 Each bit is mapped to a gun A
7 Clear Maintenance
Hour
8 Each bit is mapped to a gun A
NOTE A: Each physical gun number is assigned a bit starting with the LSBit of Data Byte #1. For example, if
Message No.1 (Trigger guns) is sent with Data Byte #1 = 0x05, Data Byte #2 = 0xF0, and the remaining
data bytes are 0, then guns #1,3,13,14,15,16 will be triggered ON. The remaining gun numbers are
triggered OFF.

Other manuals for Nordson iControl

Related product manuals