Securing Commercial Water Heating System Wall Mount
• Before mounting the CR60 to the wall, make sure the wall is capable of supporting the fully assembled
weight of the CR60.
• Consult a structural engineer for appropriate methods or structural analysis before attempting to wall
mount the fully assembled CR60.
• Failure to comply with the above requirements could result in substantial property damage, personal
injuries or death.
General Instructions for Mounting All CR60 Wall Hanging Racks
• Identify the installation location and confirm that the installation will meet all required clearances.
• There are no pre-drilled holes in the CR60 frame. Refer to the below for proper fastening instructions:
1. Identify fastening points (i.e. stud) at a maximum 18 in. apart.
2. Drill 5/16” clearance holes through the top frame of the CR60 rack corresponding to each
fastening location
3. Use ¼” x 2 ½” Wood Lag Bolts along with a ¼” flat washer (Field Supplied)
4. Tighten lag bolts
Commercial Water Heating System Wall Mount Models
• The minimum number of fastening points shall be: