4. OPERATION AND USE
The temp. Sensor is broken or
short circuit
Check or change the temp. Sensor
Ambient Temp.
Sensor Fault
The temp. Sensor is broken or
short circuit
Check or change the temp. Sensor
The temp. Sensor is broken or
short circuit
Check or change the temp. Sensor
Suction Temp.
Sensor Fault
The temp. Sensor is broken or
short circuit
Check or change the temp. Sensor
Discharge Temp.
Sensor
Fault
The temp. Sensor is broken or
short circuit
Check or change the temp. Sensor
The high-pressure switch is broken
Check the pressure switch and cold
circuit
Check the pressure switch and cold
circuit
No water/little water in water
system
Check the pipe water flow and
water pump
Check the pipe water flow and
whether water system is jammed
or not
Primary
Anti-freezing
Prot.
Secondary
Anti-freezing
Prot.
Inlet and outlet
temp. too big
Water flow is not enough
and low differential pressure
Check the pipe water flow and
whether water system is jammed
or not
Low temperature
protection
The environment temp. is low
The compressor is overload
Check whether the system of the
compressor running normally
Exhaust Air over
Temp Prot.
The compressor is overload
Check whether the system of the
compressor running normally
Communication failure between
wire controller and mainboard
Check the wire connection
between remote wire controller
and main board
Antifreeze
Temp. Sensor
Fault
antifreeze temp sensor is broken or
short circuited
check and replace this temp sensor
water temp. or ambient temp. is
too low