1-274 XPM card replacement procedures
297-8021-547 Standard 14.02 May 2001
NT2X11
in an RLCM-EDC RMM
Application
Use this procedure to replace the card that follows in the shelves or frames
identified in the table that follows.
You cannot always identify the PEC, suffix, and shelf or frame for the card you
want to replace. If this event occurs refer to the Index for a list of cards,
shelves, and frames documented in this maintenance manual.
Common procedures
The replacing a card procedure is referenced in this procedure.
Action
The following flowchart is only a summary of the procedure. To replace the
card, use the instructions in the step-action procedure that follows the
flowchart.
PEC Suffixes Cardname Shelf/frame name
NT2X11 AA, AE Line Test Unit Digital
Card (LTUD)
RMM/RLCC