4-21
Security 15088:K 03/21/01
CM Control Module for Ringback:
Address: LXXMYY (Installer specified).
Type ID: CMXC
Control-By-Event: ( )
Custom Label: Installer Specified.
Signal Silence: Yes
Walk Test: Yes/No (Installer Specified).
Annunciator: Yes
Annunciator Point: AssPm**
Figure 1.3-10 Programming Key (continued):
STS-1 Tamper Switch w/MM Module:
Address: LXXMYY (Installer specified).
Type ID: SEQM - Results in no indication
at Protected Premises Unit dis-
play. Indication at Central Station
only.
SSYM - When activated, results
in indication at PPU display and at
Central Station.
Control-By-Event: (Zaa* Zal*)
Custom Label: Installer Specified.
Tracking: Yes
Annunciator: Yes
Annunciator Point: AssPn**
= CM
ACM-16AT/-32A Annunciator:
Annun. Pt. Type ID
ArrP1 AZON
ArrP2 AZON
ArrP3 AMON
ArrP4 AMON
ArrP5 AZON
Group Interface:
A: CM programming
Address: LXXMYY (Installer specified).
Type ID: CMXC
Control-By-Event: (Zaj*)
Custom Label: Security Group Output
Signal Silence: No
Walk Test: Yes/No (Installer Specified).
Annunciator: No (Not required).
B: MM programming:
Address: LXXMYY (Installer specified).
Type ID: SARM
Control-By-Event: ( )
Custom Label: Installer Specified.
Tracking: Yes - Results in required
acknowledgment at the Protected
Premises Unit for every unsecured
state when the system is armed as
long as the event is present.
Restoral at the Protected Pre-
mises Unit is automatic.
No - Results in required acknowl-
edgment at the Protected Premises
Unit for first unsecured state only
(system armed). The system must
be manually reset at the Protected
Premises Unit or at the Central Sta-
tion - short condition only.
Annunciator: Yes
Annunciator Point: AssPp**
MM = CM