Operation
Switch Functions
16
Document 51264 Rev A2 6/14/00 P/N 51264:A2
When more than one event exists, the first press of the Acknowledge
switch silences system piezo sounders. The second press of the
switch stops the scrolling and holds the event on the display for one
minute. Subsequent pressing of the switch 'steps' through each
active event.
2.2.3 Silence
When the Silence switch is pressed and released, the FDU-80 sends
an alarm silence command to the control panel. The Silence switch
performs the same functions as the Acknowledge switch. In addition,
if an alarm exists, it turns off all silenceable NACs and causes the
FACP Alarm Silenced LED to turn on while the FDU-80 will display
a 'silenced' message. It also sends an 'Alarm Silenced' message to the
printer and the history file within the FACP. A subsequent new alarm
will resound the appropriate NACs (Notification Appliance Circuits)
and local sounders.
2.2.4 Drill: Hold 2 Sec.
When the Drill switch is pressed and held for at least two seconds
(time required to prevent accidental activations), the FDU-80 will
transmit a drill command to the control panel. This command causes
the FACP to turn on all NAC outputs and all silenceable circuits (all
control modules/NACs that are programmed silenceable). In the
event that the system was previously silenced, the drill command
will also turn off the Alarm Silenced LED. The 'Manual Evacuate'
message is shown on the FDU-80 display. The same message is sent
to the FACP display, printer and history files. The Silence switch
operates on
silenceable
NAC outputs only.
2.2.5 Reset
When the System Reset switch is pressed and released, the FDU-80
sends a Reset command to the control panel. This will turn off all
control modules and Notification Appliance Circuits, temporarily
turns off resettable power to 4-wire detectors, causes a 'System All
Normal' message to be displayed on the FDU-80 and sends a 'Sys-
tem Reset' message to the FACP display, printer and FACP history
files. It also turns on all system LEDs, piezo sounders and LCD dis-
play segments as long as the Reset switch is held (lamp test). Any
alarm or trouble that exists after a Reset will resound the system.