FDU-80 Annunciator
Features of FDU-80
7
Document 51264 Rev A2 6/14/00 P/N 51264:A2
1.1 Features of FDU-80
• 80-character LCD display (20 characters x 4 lines) is backlit
under normal and alarm conditions
• System Status LEDs for AC Power (green), Alarm (red), Trouble
(yellow), Supervisory (yellow) and Alarm Silenced (yellow)
• No programming necessary — duplicates messages at control
panel display.
Note: The FACP may require programming to function with the
FDU-80. Refer to the specific FACP manual for programming
information
• Local piezo sounder with alarm and trouble resound
• Device type identifiers from the control panel
• Device & zone custom alpha labels from the control panel
• Time/date and device address from the control panel
• EIA-485 connects to control panel terminal port
• Plug-in terminal blocks for ease of installation and service
• DIP switches control piezo enable/disable, transmit/receive
mode, FACP selection, function switches and key-switch enable/
disable.
• Up to 32 FDU-80 Annunciators per FACP
• Mounting options:
✓ Surface mounting in SBB-3 (2.75" depth) or three
electrical boxes ganged together
✓ Semi-flush mounting in three-gang electrical box (P/N
10103) with a minimum depth of 2.187" or three electrical
boxes ganged together
✓ Can be located up to 6,000 feet (1,800 m) from the panel
• Backlight turns off during AC loss to conserve battery power but
will turn back on if an alarm condition occurs.
• Enable/Disable key-switch
• Function switches for:
✓ Acknowledge/Step
✓ Alarm Silence
✓ Drill
✓ System Reset/Lamp Test