EasyManuals Logo

Novus N2000 User Manual

Novus N2000
11 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #5 background imageLoading...
Page #5 background image
Controller N2000
NOVUS AUTOMATION 5/11
Fig. 4aConnection of 4-20 mA Fig. 4b Connection of 5 Vdc
4-20 mA
Refer to Fig. 4a. (The controller provides an internal electronic shunt
for the input current. No changes in the circuit are necessary).
0-5 Vdc:
Refer to Figure 4b for connecting voltage signals.
4-20 mA:
The connections for current signals 4-20 mA must be carried-out
according to Figure 4c.
Fig. 4c -
4-20 mA transmitter using the N2000 24 Vdc supply
Remote setpoint
The remote Setpoint (SP) is enabled by an external digital signal in
either I/O5 or I/O6, when programmed with the code
rsp
(Select
remote SP input).
An external resistor shunt of 100 is required between the terminals
19 and 20.
Fig. 4d -
Connection for remote SP
(0-20 / 4-20 mA)
DIGITAL OUTPUT
I/O5 can also be configured as digital output. An example of usage is
shown in Fig. 5. I/O5 is electrically isolated from the sensor input.
Fig. 5I/O5 with output pulse for SSR.
DIGITAL INPUT
I/O5 and I/O6 can be used as digital inputs, accepting either dry contact
or NPN open collector signals. Fig. 6 shows a switch driving the I/O5
digital input. The digital input at I/O6 is driven only by dry contact
signals. Fig. 7 shows a typical digital input wiring for I/O6.
Fig. 6Digital input at I/O5 Fig. 7Digital input at I/O6
OPERATION
The front panel is shown in Fig. 8.
Fig. 8 - Front panel parts
Status display/PV: shows the value of PV (Process Variable). When
in programming mode, shows the parameter name.
Parameter display/SV: shows the SV (Setpoint Variable) value and
the value of other parameters of the controller.
COM Indicator: Flashes when communication messages are sent by
the controller.
TUNE Indicator: Lights during the execution of PID automatic tuning.
MAN Indicator: Lights when the controller is in manual.
RUN Indicator: Lights when the controller is active, with control and
alarm outputs enabled.
OUT Indicator: For relay or pulse control output, reflects the actual
state of the output. If an analog output is assigned for control, lights
continuously.
A1, A2, A3 and A4 Indicators: Status of the alarms.
P
- PROG key: used to walk through the menu cycles
- BACK key: go back to the previous displayed parameter
- INCREASE and
- DECREASE keys: Used to change
parameter values
-
AUTO/MAN KEY: Shortcut for automatic/manual control
selection. Alternates the control mode between automatic and
manual each time the key is pressed.
-
PROGRAMMABLE FUNCTION KEY: Can be assigned to the
special functions described for the
RVN , RSP, KPRG,
e
PR1
according to Table 2.
When the controller is turned on, its firmware version is displayed for
3 seconds, after which the controller starts normal operation. The
values of PV and SV are displayed and the outputs are enabled.
Before the controller is ready to be used in a given process, it
requires some basic configuration, such as:
Input type (T/C, Pt100, 4-20 mA).
Control Setpoint Value (SP).
Control Output Type (relays, 0-20 mA, 4-20 mA).
PID parameters (or hysteresis for ON / OFF control)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Novus N2000 and is the answer not in the manual?

Novus N2000 Specifications

General IconGeneral
BrandNovus
ModelN2000
CategoryController
LanguageEnglish

Related product manuals