Sensitivity Settings
The sensitivity of the E-LDA-LC2 is set at 6 (mid-range) by default. If an adjustment to this sensitivity is necessary it can be
manually adjusted.
To adjust sensitivity manually, rotate the knob on the front of the E-LDA-LC2.
At the lowest sensitivity, an alarm will be triggered by immersing the water rope in about half an inch of water.
At medium sensitivity, an alarm will be triggered the moment the water cable touches water.
At the highest sensitivity setting, an alarm can be triggered by a single spray of water.
Note: The above sensitivity settings are based on using E-LD-LCx-y and E-LDx-y. If the
E-CDx-y is used, a higher sensitivity setting to achieve the same results will be needed. (e.g. E-CDx-y requires that
the sensing rope be immersed in 1 inch of water to trigger the alarm when set at medium sensitivity.)
LED operational status indications
Flashing Operating normally RUN (green)
Sustained brightness or unlit Power is not normal or unit is failing
On Presence of leaks ALARM (red)
Off Absence of leaks
Audible Alarm
When the E-LDA-LC2 detects moisture, the E-LDA-LC2 sounds a built-in audible alarm. This alarm will sound until the
moisture is cleared, or until the "CLR" button on the E-LDA-LC2 is pressed. Once pressed, the alarm will not sound again
until the sensor state returns to normal and another moisture detection event occurs.