TRX Series II - Installation - Startup - Maintenance Instructions
Part 9 - Controls
8. 6. 1 Error list reset - Clears
Error History
Do you really want to
perform the RESET? If
you pressOK button,
the reset command will
be executed otherwise,
by way of ESC, the ore-
vious page is shown.
8. 7 FREE PARAMETERS - Read Only
8. 7. 0 NOT USED
8. 7. 1 NOT USED
8. 7. 2 NOT USED
8. 7. 3 NOT USED
8. 7. 4 Boiler flow switch 0= Open
1=
8. 7. 6 Safety flame sensor 0= OFF
1= ON
8. 7. 8 Boiler Power Level(%) 0 - 100
(0 = minimum power,
100 = maximum
power)
8. 7. 9 Ionization current
The flame signal must exceed 18 to initially detect the
presence of flame. Flame loss is detected if the signal
drops below 15.
19 WI  FI (only for ALTEAS ONE+ NET)
19.
0 WI-FI CONFIGURATION
19.
0. 0 Wi-Fi activation 0 = OFF
1 = ON
19.
0. 1 Network configuration 0 = OFF
1 = ON
19.
0. 2 <Not Available>
19.
0. 3 Internet time 0 = OFF
1 = ON
19.
0. 4 Internet heather 0 = OFF
1 = ON
19.
0. 5 On line outdoor
temperature corr.
19.
1 CONNECTIVITY INFO
19.
1. 0 Connectivity status OFF
Initialization
Idle
Acess Point initializing
Acess Point mode on
Station Mode - Connecting
Station Mode - Connected
Station Mode - Provisioning
Station Mode - Server
Connected
Wifi error
19.
1. 1 Signal level
19.
1. 2 Active Status Not provisioned
Provisioned - Not active
Active
19.
1. 3 Serial Number
19.
1. 4 SW Upgrade Status Initialization
Waiting for Update
Updating Micro 1
Updating Micro 2
19.
1. 5 On line outdoor temperature
19.
1. 6 On line weather data
19.
2 RESET MENU
19.
2. 0 Factory Reset (soft reset) Do you really want to perform
the reset? if you press OK
button, the reset command
will be executed otherwise, by
way of ESC, the previous page
is shown.
21
2-ZONE CONTROL MODULE
21.
1 2-ZONE CONTROL MODULE - TEST
21.
1. 0 Manual mode activation 0 = OFF
1 = ON
21.
1. 1 OUT1 Control 0 = OFF
1 = ON
21.
1. 2 OUT2Control 0 = OFF
1 = ON
21.
4 2-ZONE CONTROL MODULE DIAGNOSTICS
21.
4. 0 Output 1 Status 0 = OFF
1 = ON
21.
4. 1 Output 2 Status 0 = OFF
1 = ON
21.
9 2-ZONE CONTROL MODULE - CONFIGURATION
21.
9. 0 Zone outputs overrun 60 - 600 seconds
21.
9. 1 Zone outputs overrun
DHW
Table 39 - Complete Parameters List
Menu
Sub-Menu
Parameter
Description Value
Default
Setting
Note
Menu
Sub-Menu
Parameter
Description Value
Default
Setting
Note