74 | nVent.com
APPENDIX G—FACTORY DEFAULT CONFIGURATION V3.1X
910 SERIES HTC
BASIC MODE MENU
(All other parameters are set as shown in the Advanced Mode Sub-Menus)
Configuration Mode Menu
Parameter Factory User
Control Setpoint 68°F (20°C)
Lo TS 1 14°F (–10°C)
Lo Load 1.0A
Switch Control Mode Deadband
Circuit Breaker *n/a (30.0A)
Temperature Units °F
Feature Mode Basic
ADVANCED MODE MENUS
Configuration Mode Main Menu
Parameter Factory User
Control Setpoint 68°F (20°C)
Lo TS 1 14°F (–10°C)
Lo Load 1.0 A
Hi GFI 20 mA
GFI Trip 30 mA
Feature Mode Advanced
TS Alarms Configuration Sub-Menu
Parameter Factory User
TS 1 Fail Enable
Lo TS 1 Enable
Lo TS 1 14°F (–10°C)
Hi TS 1 Disable
Hi TS 1 *n/a
(212°F (100°C))
TS 2 Fail Disable
Lo TS 2 Disable
Lo TS 2 *n/a
(14°F (–10°C))
Hi TS 2 Disable
Hi TS 2 *n/a
(212°F (100°C))
Lo TS Filter 0 min
Hi TS Filter *n/a (0 min)
Latch TS Alarms Yes
CTL TS Fail Enable