76 | nVent.com
Point Setup Sub-Menu
Parameter Factory User
Tag TAG -(factory ID)
Switch Control Mode Deadband
Prop Band *n/a (4°F (2°C))
Deadband 5°F (3°C)
Cycle Time *n/a (10 min)
Switch Rating *n/a (30.0 A)
Circuit Breaker *n/a (30.0 A)
Max Power *n/a (7200 W)
TS Fail Mode Off
TS CTL Mode TS1-Fail Off
TS1Type 100ΩPlat
TS1LeadResist *n/a(0)Ω
TS 1 Hi Limit Disable
TS2Type 100ΩPlat
TS2LeadResist *n/a(0Ω)
TS 2 Hi Limit Disable
Autocycle Enable
Autocycle Interval 8
Autocycle Units Hours
Override Source Remote
Load Shedding Disable
Miscellaneous Setup Sub-Menu
Parameter Factory User
Temperature Units °F
Version V3.1x.xx n/a
Ext. Input Not used
Flash Alarm Output Yes
Alarm Output N.C.
Language English
Passcode 0
Scroll Delay 0.15 sec
Load Defaults (See user manual)
Communications Setup Sub-Menu
Parameter Factory User
Protocol HTCBUS
HTCBUS Addr (factory ID)
Modbus Addr *n/a (1)
Modbus Sub Addr *n/a (0)
Baud Rate Auto
Parity *n/a (None)
Hardware None, modem, RS-232, RS-485 n/a
Driver Auto
Profile Auto
Tx Delay 0.06 sec
*n/a: Parameter may only appear if certain features are enabled. Values shown in brackets are the
Factory defaults if the settings are enabled. This information defines the default 910 Series Control
Module configuration as set by the Factory for firmware V3.1X. These settings are subject to change
without notice. It is the user’s responsibility to verify that all configuration parameters are chosen
appropriately for the intended application.