8000 BTU/HR. UNIT CHARACTERISTICS
Model
G520816GXXX G520826GXXX
Dimensional Data
Height 52.69” / 1338.4 mm
Width 17.12” / 435 mm
Depth 11.66” / 296.1 mm
Unit Weight 128 lbs / 58.1 kg
Unit Protection Rating Type 12/4/4X/3R
Cooling Data
Refrigerant R134A
Refrigerant Charge 20 oz. 24 oz.
Cooling Capacity at 95 F Enclosure
95 F Ambient (BTU/Hr./W)
6100 / 6800 7035 / 7450
Cooling Capacity at Max Conditions
(BTU/Hr./W)
7600 / 8350 8360 / 8800
Maximum Ambient Temp 131 F / 55 C
Minimum Ambient Temp -40 F / -40 C
Enclosure Airow 285 / 310 CFM
External Airow 650 / 700 CFM
Condensate Management Hose discharge / Optional powered C/E
Heating Data
Capacity 2000W
Electrical Data
Rated Voltage (50/60 Hz) 115V 230/208-230V
Rated Frequency 50 / 60 Hz
Voltage Range +/- 10% of rated
Cooling Amps at Max Conditions 9.9 / 11.4 5.2 / 6.9-6.6
Heating Amps 17.3 9.6
Compressor RLA / LRA 5.4 / 38.0 3.7 / 19.0
Evaporator Fan RLA* .5 .3
Condenser Fan RLA* .5 .3