EasyManua.ls Logo

nvent SPECTRACOOL G52 - 12000 BTU;HR UNIT CHARACTERISTICS

nvent SPECTRACOOL G52
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
© 2022 nVent
89209668
- 33 -
12000 BTU/HR. UNIT CHARACTERISTICS
Model
G521216GXXX G521226GXXX
Dimensional Data
Height 52.69” / 1338.4 mm
Width 17.12” / 435 mm
Depth 11.66” / 296.1 mm
Unit Weight 131 lbs / 59.4 kg
Unit Protection Rating Type 12/4/4X/3R
Cooling Data
Refrigerant R134A
Refrigerant Charge 38 oz. 36 oz.
Cooling Capacity at 95 F Enclosure
95 F Ambient (BTU/Hr./W)
9455 / 10433 9220 / 9920
Cooling Capacity at Max Conditions
(BTU/Hr./W)
11761 / 12700 11000 / 11700
Maximum Ambient Temp 131 F / 55 C
Minimum Ambient Temp -40 F / -40 C
Enclosure Airow 287 / 305 CFM
External Airow 635 / 650 CFM
Condensate Management Hose discharge / Optional powered C/E
Heating Data
Capacity 2000W
Electrical Data
Rated Voltage (50/60 Hz) 115V 230/208-230V
Rated Frequency 50 / 60 Hz
Voltage Range +/- 10% of rated
Cooling Amps at Max Conditions 15.5 / 19.7 8.0/10.9-10.2
Heating Amps 17.3 9.6
Compressor RLA / LRA 10.0 / 60.0 6.2 / 30.0
Evaporator Fan RLA* .5 .3
Condenser Fan RLA* .5 .3