56
ENGLISH
3
Parameter DISPLAY
MNEMONIC
MENU Range of
adMustment
Factory
setting
COMMENTS
COOLING CLIMATE
CURVE FOR MAXIMUM
WATER TEMPERATURE
Cc1 Service -15 – +50°C 20°C Factory settings for
fan coils and control of
systems with leaving
water temperature
(LUc1)
Cc3Cc1; Cc2Cc4
OUTSIDE AIR COOLING
CLIMATE CURVE FOR
MAXIMUM WATER
TEMPERATURE
Cc2 Service Luc0:
4°C -20°C,
Luc1:
7°C -27°C
18°C
OUTSIDE AIR COOLING
CLIMATE CURVE FOR
MINIMUM WATER
TEMPERATURE
Cc3 Service -15 – +50°C 40°C
COOLING CLIMATE
CURVE FOR MINIMUM
WATER TEMPERATURE
Cc4 Service Luc1:
4°C -20°C,
Luc0:
7°C -27°C
15°C
OUTSIDE AIR HEATING
CLIMATE CURVE FOR
MAXIMUM WATER
TEMPERATURE
Hc1 Service -15 – +50°C -5°C Factory settings for
fan coils and control of
systems with leaving
water temperature
(LUc1)
Hc3Hc1; Hc2Hc4
HEATING CLIMATE
CURVE FOR MAXIMUM
WATER TEMPERATURE
Hc2 Service Luc1:
20-60°C,
Luc0:
20-55°C
35°C
OUTSIDE AIR HEATING
CLIMATE CURVE FOR
MINIMUM WATER
TEMPERATURE
Hc3 Service -15 – +50°C 20°C
HEATING CLIMATE
CURVE FOR MINIMUM
WATER TEMPERATURE
Hc4 Service Luc1:
20-60°C,
Luc0:
20-55°C
28°C
SERVICE MENU
PASSWORD
PAS Service Value held by Olimpia
Splendid Service
rtF Service 0 – 200
(step 10)
0 FACTOR USE, DO
NOT MODIF
PERIPHERAL ADDRESS Adr Service 1 – 255 1 RS485 communication
port address to be used
with any remote control
peripheral (PC or the
like)