2
Ratings and Specifications
*The ambient operating illumination is the illumination that changes the output ±20% at 200 lx. It is not the operational limit.
Sensing method Through-beam
Retro-re-
flective
Diffuse-reflective Convergent-reflective
Item
Model
E3S-2E4
E3S-2E41
E3S-5E4
E3S-5E41
E3S-R2E4
E3S-R2E41
E3S-
DS10E4
E3S-
DS10E41
E3S-
DS30E41
E3S-
DS30E4S
E3S-
LS10XE4
E3S-
LS20XE4
Sensing distance 2 m 5 m 0.1 to 2 m
100 mm
(white paper
50 x 50 mm)
300 mm
(white paper 100 x 100)
30 to 100 mm
Continuously
variable
(10 x 10 mm)
50 to 250 mm
Continuously
variable
(50 x 75 mm)
Standard sensing
object
Opaque: 7-
mm dia. min.
Opaque: 11-
mm dia. min.
Opaque: 30-
mm dia. min.
Transparent, opaque
Differential travel --- 20% max. of setting distance
1.5 mm max.
at 30 mm
5% max. at 50
to 250 mm
10 mm max.
at 100 mm
Directional angle
Both emitter and receiver:
3° to 10°
3° to 10° ---
Light source
(wavelength)
Infrared LED
(950 nm)
RED LED
(660 nm)
Infrared LED
(950 nm)
Power supply
voltage
12 to 24 VDC ±10%, ripple (p-p): 10% max.
Current
consumption
50 mA max.
(Emitter: 25 mA max.,
Receiver: 25 mA max.)
40 mA max.
Control output
(solid-state out-
put)
Output current: 1.5 to 4 mA, Load current: 80 mA max. (residual voltage: 2 V max.) Refer to page 4.
Response time Operate or reset: 3 ms max. Operate or reset: 1 ms max.
Sensitivity
adjustment
With an indicator
Ambient
illumination
(Receiver side) *
Incandescent lamp: 3,000 lx max.
Sunlight: 10,000 lx max.
Ambient
temperature
Operating: 25 to 55°C, Storage: 40 to 70°C (with no icing or condensation)
Ambient humidity Operating: 35% to 85%, Storage: 35% to 95% (with no condensation)
Insulation
resistance
20 MΩ min. at 500 VDC
Dielectric strength 1,000 VAC, 50/60 Hz for 1 min
Vibration
resistance
(destruction)
10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
Shock resistance
(destruction)
500 m/s
2
3 times each in X, Y, and Z directions
Degree of
protection
IEC IP65 IEC IP67 IEC IP65 IEC IP67
Connection
method
Pre-wired cable (standard length: 2 m)
Indicators Light indicator (red), Stability indicator (green)
Material
Case
Polybuty-
lene tereph-
thalate
Zinc die-cast
Polybuty-
lene tereph-
thalate
Zinc die-cast
Lens * Polycarbonate
Mount-
ing
Bracket
Iron

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E3S and is the answer not in the manual?

Omron E3S Specifications

General IconGeneral
Output TypeNPN or PNP
Response Time1 ms max
Light SourceInfrared LED
Protection CircuitReverse polarity protection
Output Current100 mA max.
Operating Temperature-25 to 55 °C
Storage Temperature-40 to 70 °C
Housing MaterialABS
Connectionconnector