5   Advanced Operations
5 - 24
E5@C Digital Temperature Controllers User’s Manual (H174)
5-9 OR Output of Alarms
You can use an integrated alarm to output an OR of alarms 1 to 4, the HB alarm, the HS alarm, the
input error, and the RSP input error. Set the Integrated Alarm Assignment parameter (alma) and then
assign the integrated alarm (alm) to an auxiliary output or a control output.
 Parameters
5-9-1 Integrated Alarm
Parameter
No. 1 
display
Value
No. 2 
display
Level
Control Output 
Assignment
out1 to 
out2
ALM: Integrated alarm (The Integrated 
Alarm Assignment parameter must be 
set separately.)
alm
Advanced 
Function Setting 
Level
Auxiliary 
Output 1 to 4 
Assignment
sub1 to 
sub4
ALM: Integrated alarm (The Integrated 
Alarm Assignment parameter must be 
set separately.)
alm
Advanced 
Function Setting 
Level
Integrated 
Alarm 
Assignment
alma
Set the sum of the following values for 
the alarms and errors to include in the 
OR output. 0 to 255
Alarm 1: +1
Alarm 2: +2
Alarm 3: +4
Alarm 4: +8
HB alarm: +16
HS alarm: +32
Input error: +64
RSP input error: +128
(Default: 49 (i.e., an OR of alarm 1, the 
HB alarm, and the HS alarm))
0 to 255
Advanced 
Function Setting 
Level