A   Appendices
A - 22
E5@C Digital Temperature Controllers User’s Manual (H174)
If the Digital Controller is not operating normally, check the following points before requesting repairs. If
the problem persists, contact your OMRON representative for details on returning the product.
*1 Also refer to the E5
@
C Digital Controllers Communications Manual (Cat. No. H175) for details.
A-5-2 Checking Problems
Timing Status Meaning Countermeasures Page
Turning 
ON the 
power for 
the first 
time
The TUNE indicator will 
flash.
ST (self-tuning) is in 
progress (default setting: 
ON).
This is not a product fault.
The TUNE indicator flashes during self-tuning.
4-27
Temperature error is 
large.
Input error (S.Err display)
Input type mismatch Check the sensor type and reset the input type correctly. 4-12
Thermometer is not 
installed properly.
Check the thermometer installation location and polarity 
and install correctly. 
2-25, 
2-41
Communications are not 
possible.
Non-recommended 
adapter is being used.
Make sure that the connected device is not faulty.
*
1
During 
operation
Overshooting
Undershooting
Hunting
ON/OFF control is 
enabled (default: ON/OFF 
control selected).
Select PID control and execute either ST (self-tuning) or 
AT (auto-tuning). 
When using self-tuning, turn ON the power supply to the 
Digital Controller and load (heater, etc.) at the same time, 
or turn ON the load power supply first. Accurate 
self-tuning and optimum control will not be possible if the 
power supply to the load is turned ON after turning ON the 
power supply to the Digital Controller. 
4-24
Control period is longer 
compared with the speed 
of rise and fall in 
temperature.
Shorten the control period. A shorter control period 
improves control performance, but a cycle of 20 ms 
minimum is recommended in consideration of the service 
life of the relays.
4-15
Unsuitable PID constant Set appropriate PID constants using either of the following 
methods.
• Execute AT (autotuning).
• Set PID constants individually using manual settings.
4-24
HS alarm operation fault Use breeder resistance if the problem is due to leakage 
current. Also investigate the errors detected by the HS 
alarm function.
4-42
Temperature is not rising Specified operation is 
unsuitable for required 
control (default: Reverse 
operation).
Select either forward or reverse operation depending on 
the required control. Reverse operation is used for heating 
operations.
4-15
Heater is burnt out or 
deteriorated.
Check whether heater burnout or deterioration have 
occurred. Also investigate the errors detected by the 
heater burnout alarm.
4-40
Insufficient heater 
capacity
Check whether the heater's heating capacity is sufficient. ---
Cooling system in 
operation.
Check whether a cooling system is operating. ---
Peripheral devices have 
heat prevention device 
operating.
Set the heating prevention temperature setting to a value 
higher than the set temperature of the Digital Controller.
---
The AT Execute/Cancel 
parameter (at) is not 
displayed.
ON/OFF control is 
enabled.
Set the PID ON/OFF parameter to PID. 6-45
The Controller is stopped. Set the RUN/STOP parameter to RUN. 6-13
The SP Ramp Set Value 
parameter (sprt) is not 
displayed.
ST is enabled Set the ST parameter to OFF. 6-33
The Remote SP Enable 
parameter (rspu) is not 
displayed.
ST is enabled Set the ST parameter to OFF. 6-85
The Alarm 1 Type 
parameter (alt1) is not 
displayed.
The Auxiliary Output 1 
Assignment parameter is 
set to a heater alarm for a 
Controller with heater 
burnout detection.
Set the Auxiliary Output 1 Assignment parameter to Alarm 
1. The default setting is for a heater alarm (HA).
6-83