EasyManuals Logo

Omron E5CC User Manual

Omron E5CC
440 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #160 background imageLoading...
Page #160 background image
4 Basic Operation
4 - 18
E5@C Digital Temperature Controllers User’s Manual (H174)
Assign the control outputs and auxiliary outputs.
Control output 1: Control output (heating)
Control output 2: Control output (cooling)
Auxiliary output 1: Alarm 1
Auxiliary output 2: Alarm 2
Operating Procedure
Setting Heating/Cooling Control
1
Press the M Key several times in the Initial Setting Level to
display s-hc (Standard or Heating/Cooling).
Initial Setting Level
2
Press the U or D Key to set the parameter to h-c.
The default is stnd (standard).
*
Use the following procedures to check the output assignments. The output
assignments are changed automatically when you change between stan-
dard and heating/cooling control. You do not have to set them.
Setting Control Output 1
1
Press the M Key several times in the Advanced Function
Setting Level to display out1 (Control Output 1 Assignment).
Advanced Function Setting
Level
2
Set the parameter to o (Control Output (Heating)).
The default is o (Control Output (Heating)).
Setting Control Output 2
1
Press the M Key several times in the Advanced Function
Setting Level to display out2 (Control Output 2 Assignment).
Advanced Function Setting
Level
2
Set the parameter to c-o (Control Output (Cooling)).
As soon as you select h-c (Heating/Cooling) for the Standard or
Heating/Cooling parameter, the setting of this parameter is
automatically changed to c-o (Control Output (Cooling)).
Setting Auxiliary Output 1
1
Press the M Key several times in the Advanced Function
Setting Level to display sub1 (Auxiliary Output 1 Assignment).
Advanced Function Setting
Level
2
Press the U or D Key to set the parameter to alm1.
The default is alm1 (Alarm 1).
If the Digital Controller is equipped with HB/HS alarm detection,
this parameter is set by default to ha (heater alarm).
stnd
5-hc
Standard or
Heating/Cooling
h-c
5-hc
o
out1
Control Output
1 Assignment
o
out1
c-o
out2
Control Output
2 Assignment
c-o
out2
alm1
sub1
Auxiliary Output
1 Assignment
alm1
sub1

Table of Contents

Other manuals for Omron E5CC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CC and is the answer not in the manual?

Omron E5CC Specifications

General IconGeneral
Number of Display Digits4 digits
Number of Control Outputs1
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage, Analog current
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Display TypeLCD
Size48 x 48 mm
Mounting MethodPanel mount
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25% to 85% RH
Protection RatingIP66

Related product manuals