6 - 5
6 Parameters
E5@C Digital Temperature Controllers User’s Manual (H174)
6-2 Protect Level
6
Changes to settings using key operations are restricted.
* If the setting of a parameter is changed back to its default setting, it will no longer be displayed. To display it
again, set the Changed Parameters Only parameter to OFF.
wtpt
Setting Change Protect
The Event Input Assignment 1 to Event Input
Assignment 6 parameters must not be set to
enable/disable setting changes.
Change Setting Protect
This parameter is not displayed if the Event Input Assignment 1 to Event Input
Assignment 6 parameters are set to enable/disable setting changes.
The all protect indication ( ) will light when setting is ON.
pfpt
PF Key Protect
PF Key Protect
This parameter enables and disables PF Key operation.
chgp
Changed Parameters Only
This parameter allows you to display only the parameters that have been changed from
their default settings.
Function
Setting
Set value Description
OFF (default) Settings can be changed using key operations.
ON Settings cannot be changed using key operations. (The protect level
settings, however, can be changed.)
Function
Setting
Set value Description
OFF (default) PF Key enabled
ON PF Key disabled (Operation as a function key is prohibited.)
Function
Setting
Setting range Default
on: Enabled, off: Disabled off

Table of Contents

Other manuals for Omron E5CC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CC and is the answer not in the manual?

Omron E5CC Specifications

General IconGeneral
Number of Display Digits4 digits
Number of Control Outputs1
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage, Analog current
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Display TypeLCD
Size48 x 48 mm
Mounting MethodPanel mount
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25% to 85% RH
Protection RatingIP66