EasyManuals Logo

Omron E5CC User Manual

Omron E5CC
440 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #45 background imageLoading...
Page #45 background image
2 - 7
2 Preparations
E5@C Digital Temperature Controllers User’s Manual (H174)
2-1 Installation
2
2-1-2 Panel Cutout (Unit: mm)
E5DC/E5DC-B
E5GC
The E5CC-U, E5DC, and E5DC-B cannot be waterproofed.
Waterproofing is not possible when group mounting several Digital Controllers.
The recommended panel thickness is 1 to 5 mm for the E5CC, E5CC-U, and E5CC-B, and 1 to 8 mm
for E5EC, E5EC-B, E5AC, E5DC, E5DC-B, and E5GC.
Except for the E5GC with a screwless clamp terminal block, Digital Controllers must not be group
mounting vertically. (Observe the recommended mounting space limits.)
When two or more Digital Controllers are mounted, make sure that the ambient temperature of the
Digital Controllers does not exceed the allowable operating temperature specified in the
specifications.
*1 For E5EC models with two control outputs (QQ, QR, CQ, RR, CC, or PR) and 011, 012, 013, or 014 options
(shown below), the ambient temperature for group mounting must be 45°C max.
120 min.
Individual Mounting
Two-Unit Mounting Group Mounting
22.7
+0.3
0
45
+0.6
0
92
+0.8
0
92
+0.8
0
92
+0.8
0
(22.5 x number of Units)
+1.0
0
Individual Mounting Horizontal Group
Mounting
*2
Vertical Group Mounting
*2
22.2
+0.3
+0
40 min.
22.2
+0.3
+0
45
+0.6
+0
L1
45
+0.6
+0
L2
+1.0
+0
L1=(48×n-2.5)
+1.0
+0
L2=(24×n-1.5)
n: Number of mounted Controllers (2
n
6)
E5EC-@@ @ @ @ M-@@@
QQ, QR,
RR, CC, CQ, PR
011, 012,
013, 014

Table of Contents

Other manuals for Omron E5CC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5CC and is the answer not in the manual?

Omron E5CC Specifications

General IconGeneral
Number of Display Digits4 digits
Number of Control Outputs1
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage, Analog current
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Display TypeLCD
Size48 x 48 mm
Mounting MethodPanel mount
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25% to 85% RH
Protection RatingIP66

Related product manuals