EasyManua.ls Logo

Omron E5CN-H

Omron E5CN-H
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Com Data
for Modbus
6.1 Variable Area (Setting Range) List
6-7
Note 1: For Controllers with two event inputs (events 1 and 2), this parameter cannot be set if the Bank Numbers Used parameter
is set to a value greater than 0.
Note 2: For Controllers with two event inputs (events 1 and 2), this parameter cannot be set if the Bank Numbers Used parameter
is set to a value greater than 1.
Note 3: For Controllers with two event inputs (events 3 and 4), this parameter cannot be set if the Bank Numbers Used parameter
is set to a value greater than 0.
Note 4: For Controllers with two event inputs (events 3 and 4), this parameter cannot be set if the Bank Numbers Used parameter
is set to a value greater than 1.
Note 5: PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.
Note 6: P.END (program end output) can be set even when the program pattern is set to OFF, but the function will be disabled.
Note 7: The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.
Note 8: The setting (monitor) range depends on the transfer output type setting. (See the setting data list for details.)
Address
Parameter name Setting (monitor) value Level
Four-byte
mode
Two-byte
mode
0E14 2E0A Event Input Assignment 1
(See note 1.)
H'00000000 (0): None
H'00000001 (1): RUN/STOP
H'00000002 (2): Auto/manual switch
H'00000003 (3): Program start (See note 5.)
H'00000004 (4): Direct/reverse operation
H'00000005 (5): SP mode
H'00000006 (6): 100% AT execute/cancel
H'00000007 (7): 40% AT execute/cancel
H'00000008 (8): Setting change enable/disable
H'00000009 (9): Communications writing enabled/disabled
H'0000000A (10): Alarm latch cancel
Initial
setting
0E16 2E0B Event Input Assignment 2
(See note 2.)
H’00000000 to H’0000000A (0 to 10)
* Same as for Event Input Assignment 1.
0E18 2E0C Event Input Assignment 3
(See note 3.)
H’00000000 to H’0000000A (0 to 10)
* Same as for Event Input Assignment 1.
0E1A 2E0D Event Input Assignment 4
(See note 4.)
H’00000000 to H’0000000A (0 to 10)
* Same as for Event Input Assignment 1.
0E20 2E10 Auxiliary Output 1 Assignment H'00000000 (0): Not assigned
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Program end output (See note 6.)
H'00000007 (7): Control output ON/OFF count alarm (See note 7.)
H'00000008 (8): Work bit 1
H'00000009 (9): Work bit 2
H'0000000A (10): Work bit 3
H'0000000B (11): Work bit 4
H'0000000C (12): Work bit 5
H'0000000D (13): Work bit 6
H'0000000E (14): Work bit 7
H'0000000F (15): Work bit 8
Advanced
function
setting
0E22 2E11 Auxiliary Output 2 Assignment H’00000000 to H’0000000F (0 to 15) (Same settings as the Auxiliary Output 1
Assignment)
0E24 2E12 Auxiliary Output 3 Assignment H’00000000 to H’0000000F (0 to 15) (Same settings as the Auxiliary Output 1
Assignment)
0E28 2E14 Transfer Output Upper Limit H'FFFFF831 to H'0000270F (
1999 to 9999)
H'FFFFB1E1 to H'00007E90 (
19999 to 32400) (See note 8.)
Initial
setting
0E2A 2E15 Transfer Output Lower Limit H'FFFFF831 to H'0000270F (
1999 to 9999)
H'FFFFB1E1 to H'00007E90 (
19999 to 32400) (See note 8.)

Table of Contents

Other manuals for Omron E5CN-H

Related product manuals