SECTION 6 Communications Data for Modbus
6-12
Note 1: This parameter can be set only for ON/OFF control.
Address
Parameter name Setting (monitor) value Level
Four-byte
mode
Two-byte
mode
1348 3324 LBA Detection Time
(See note 1.)
H'00000000 to H'0000270F (0 to 9999) Advanced
function
setting
134A 3325 LBA Level Temperature: H'00000001 to H'00007E90 (0.1 to 3240.0)
Analog: H'00000001 to H'0000270F (0.01 to 99.99)
134C 3326 LBA Band Temperature: H'00000000 to H'00007E90 (0.0 to 3240.0)
Analog: H'00000000 to H'0000270F (0.00 to 99.99)
134E 3327 Soak Time Unit H'00000000 (0): Minutes
H'00000001 (1): Hours
1350 3328 Alarm SP Selection H'00000000 (0): Set point during SP ramp
H'00000001 (1): Set point
1352 3329 Remote SP Enable H'00000000 (0): OFF
H'00000001 (1): ON
1354 332A Remote SP Input Error Output H'00000000 (0): OFF
H'00000001 (1): ON
1356 332B Manual MV Limit Enable H'00000000 (0): OFF
H'00000001 (1): ON
1358 332C Direct Setting of Position Propor-
tional MV
H'00000000 (0): OFF
H'00000001 (1): ON
135A 332D PV Rate of Change Calculation
Period
H'00000001 to H'000003E7 (1 to 999)
135C 332E Automatic Cooling Coefficient
Adjustment
H'00000000 (0): OFF
H'00000001 (1): ON
135E 332F Heater Overcurrent Use H'00000000 (0): OFF
H'00000001 (1): ON
1360 3330 Heater Overcurrent Latch H'00000000 (0): OFF
H'00000001 (1): ON
1362 3331 Heater Overcurrent Hysteresis H'00000001 to H'000001F4 (0.1 to 50.0)
1364 3332 Control Output 1 ON/OFF Count
Alarm Set Value
H'00000000 to H'0000270F (0 to 9999)
1366 3333 Control Output 2 ON/OFF Count
Alarm Set Value
H'00000000 to H'0000270F (0 to 9999)