10 Temperature Controllers E5CSZ
(2) Using the E5CSZ in Devices for Fahrenheit-scale Users
(Displaying in °F)
Turn ON switch 6 to display temperatures in
°F.
Temperature Range for °F
The temperature is set to °F using the same temperature range switch as °C.
Note: The control range for multi-input (thermocouple/platinum resistance thermometer) models is
40 to +40°F of each temperature range.
(3) Setting Input Shift
Turn ON switch 4, and after turning ON the power, press the Mode
Key until h0 (indicates input shift of 0) is displayed. Press the Up and
Down Keys to set the shift value.
Shift Example
Note: When control mode switch 4 is turned OFF (no input shift
display), the input shift is not displayed but the shift value is
enabled. To disable input shift, set the input shift value to h0.
The shift range depends on the setting unit.
5. Protect Switch
When the protect switch is ON, Up Key and Down Key operations are prohibited to prevent setting mistakes.
654321
ON
Multi-input (Thermocouple/
Platinum Resistance
Thermometer)
Control mode switch 5: OFF
Multi-input (Thermocouple/
Platinum Resistance
Thermometer)
Control mode switch 5: ON
Set-
ting
°FSet-
ting
°F
0K
99 to 1999 0 Pt100 99 to 1500
1 0.0 to 199.9 1 0.0 to 199.9
2J
99 to 1500 2 99 to 99
3 0.0 to 199.9 3 0 to 200
4L
99 to 1500 4 0 to 400
654321
ON
Input shift display Measured temperature Temperature
display
h0 (no shift) 100
°C 100°C
h9 (+9
°C shift) 100°C 109°C
l9 (
9°C shift) 100°C91°C
Setting unit 1
°C0.1°C
Compensation range
99 to +99°C 9.9 to +9.9°C
Input shift display L99 to H99 L9.9 to H9.9
P
ON
X123456
Protect Switch