Temperature Controllers E5CSZ 13
Comparison with E5CST
■ Model Number Legend
■ Display
The display digits can be increased up to 1,999.
The display “ON” has changed to “OUT” and “AL” has changed to “ALM.”
■ Functions
The control outputs for relay outputs have been changed from SPDT (single-pole, double-throw) to SPST-NO (single-pole, single-throw, normally
open) contacts.
The control method has been changed to 2-PID control.
An auto-tuning (AT) function has been added.
The deviation display flashes during self-tuning (ST) and auto-tuning (AT).
The output change period has been improved from 2 s to 0.5 s.
■ External Dimensions
The depth has been shortened from 100 mm to 76 mm.
Previous model E5CSZ
Classification Symbol Meaning Classification Symbol Meaning
1 Control output R
Q
Relay: SPDT (single-pole,
double-throw)
Voltage
1 Control output R
Q
Relay: SPST-NO (single-pole,
single-throw, normally open)
Voltage
2 Alarm output 1 One alarm 2 Alarm output Blank
1
No alarms
One alarm
3 Input type KJ
P
Thermocouple (K, J)
Platinum resistance
thermometer (Pt100,
JPt100)
3 Input type T Multi-input (thermocouple/
platinum resistance
thermometer) models
Main Differences
Terminal block models use the model number E5CSZ.
The suffix “D” is added to models with a supply voltage of
24 VAC/VDC.
The suffix “B” is added to models with a black case.
4 Voltage
specifications
Blank
D
100 to 240 VAC
24 VAC/VDC
5 Case color Blank
B
Light gray
Black
1 2 3
E5CST-@@@
1 2 3
E5CSZ-@@@@-@
4 5
Previous model E5CSZ
ALALSP