2 Temperature Controllers E5CSZ
Ordering Information
■ List of Models
Note: Modules are available with a black case. Add the suffix “-B” to models with a black case.
■ Accessories (Order Separately)
Protective Cover
Terminal Cover
Specifications
■ Ratings
Size Power supply
voltage
Number of
alarm points
Control output TC/Pt multi-input
Case color: Light gray
1/16 DIN
48
× 48 × 78 mm
(W
× H × D)
100 to 240 VAC 0 Relay E5CSZ-RT
Voltage (for driving SSR) E5CSZ-QT
1 Relay E5CSZ-R1T
Voltage (for driving SSR) E5CSZ-Q1T
24 VAC/VDC 0 Relay E5CSZ-RTD
Voltage (for driving SSR) E5CSZ-QTD
1 Relay E5CSZ-R1TD
Voltage (for driving SSR) E5CSZ-Q1TD
Type Model
Hard Protective Cover Y92A-48B
Model
E53-COV10
Supply voltage 100 to 240 VAC, 50/60 Hz 24 VAC/VDC, 50/60 Hz
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 5 VA 3 VA/2 W
Sensor input Multi-input (thermocouple/platinum resistance thermometer) type: K, J, L, Pt100
Control
output
Relay output SPST-NO, 250 VAC, 3A (resistive load)
Voltage output (for driving the SSR) 12 VDC, 21 mA (with short-circuit protection circuit)
Control method ON/OFF or 2-PID (with auto-tuning)
Alarm output SPST-NO, 250 VAC, 1A (resistive load)
Setting method Digital setting using front panel keys
Indication method 3.5 digit, 7-segment digital display (character height: 13.5 mm) and deviation indicators
Other functions
• Setting change prohibit (key protection)
• Input shift
• Temperature unit change (°C/°F)
• Direct/reverse operation
• Temperature range, Sensor switching (K/J/L, Pt100)
• Switching is performed between a thermocouple and platinum resistance thermometer for multi-input models.
• Control period switching
• 8-mode alarm output
• Sensor error detection
Ambient temperature
−10 to 55°C (with no condensation or icing)
Ambient humidity 25% to 85%
Storage temperature
−25 to 65°C (with no condensation or icing)