Temperature Controllers E5CSZ 15
Alarm Mode Switch (Alarm Model Only)
Temperature Range Switch
Previous model E5CSZ
Function Selection 4
Alarm
Modes
Lower-limit
ON
Upper-limit
OFF
X
SP
ON
OFF
SP
X
ON
OFF
0
1
2
3
4
5
6
7
8
9
Set
value
Alarm type Alarm output operation
0, 9 Alarm function OFF OFF
1
Upper- and lower-
limit
2
Upper-limit
3
Lower-limit
4
Upper- and lower-
limit range
5
Upper- and lower-
limit with standby
sequence (See note
2.)
6
Upper-limit with
standby sequence
(See note 2.)
7
Lower-limit with
standby sequence
(See note 2.)
8
Absolute-value
upper-limit
X
SP
X
ON
OFF
SP
X
ON
OFF
X
SP
ON
OFF
X
SP
X
ON
OFF
X
SP
X
ON
OFF
X
SP
ON
OFF
X
SP
ON
OFF
0
Y
ON
OFF
Function selection 5 6
Temperature
Range
KJ J: 0 to 300
°CONON
K: 0 to 999
°COFFON
K: 0 to 500
°CONOFF
K: 0 to 300
°C OFF OFF
P --- ON ON
Pt100: 0 to 300
°COFFON
Pt100: 0.0 to 99.0
°CONOFF
Pt100: 0.0 to 50.0
°C OFF OFF
0
1
2
3
4
5
6
7
8
9
Set
value
Temperature Range
0 Control Mode
Switch 5: OFF
K: 0 to 1,300°C/−99 to 1,999°F
1 K: 0.0 to 199.9
°C/0.0 to 199.9°F
2J:
−99 to 850°C/−99 to 1,500°F
3 J: 0.0 to 199.9
°C/0.0 to 199.9°F
4L:
−99 to 850°C/−99 to 1,500°F
0 Control Mode
Switch 5: ON
Pt100: −99 to 850°C/−99 to 1,500°F
1 Pt100: 0.0 to 199.9
°C/0.0 to 199.9°F
2Pt100:
−99 to 99°C/−99 to 99°F
3 Pt100: 0 to 200
°C/0 to 200°F
4 Pt100: 0 to 400
°C/0 to 400°F