E5jK-T
E5jK-T
30
Specifications
 Input Type
Set
 the code according to the following table. Default is
 “2: K1 ther
-
mocouple.”
Platinum Resistance Thermometer
Set Input
 t
pe
value
u
 
0 JPt100
–199.9 to 650.0 (
°C)
/–199.9 to 999.9 (
°F)
Platinum
resistance
1 Pt100
–199.9 to 650.0 (
°C)
/–199.9 to 999.9 (
°F)
thermometer
2 K1
–200 to 1,300 (
°C)
/–300 to 2,300 (
°F)
Thermocouple
3 K2
0.0 to 500.0 (
°C)
/0.0 to 900.0 (
°F)
4 J1
–100 to 850 (
°C)
/–100 to 1,500 (
°F)
5 J2
0.0 to 400.0 (
°C)
/0.0 to 750.0 (
°F)
6 T
–199.9 to 400.0 (
°C)
/–199.9 to 700.0 (
°F)
7 E
0 to 600 (
°C)
/0 to 1,100 (
°F)
8 L1
–100 to 850 (
°C)
/–100 to 1,500 (
°F)
9 L2
0.0 to 400.0 (
°C)
/0.0 to 750.0 (
°F)
10 U
–199.9 to 400.0 (
°C)
/–199.9 to 700.0 (
°F)
11 N
–200 to 1,300 (
°C)
/–300 to 2,300 (
°F)
12 R
0 to 1,700 (
°C)
/0 to 3,000 (
°F)
13 S
0 to 1,700 (
°C)
/0 to 3,000 (
°F)
14 B
100 to 1,800 (
°C)
/300 to 3,200 (
°F)
15 W
0 to 2,300 (
°C)
/0 to 4,100 (
°F)
16 PLII
0 to 1,300 (
°C)
/0 to 2,300 (
°F)
17
4 to 20 mA
Current input
18
0 to 20 mA
19
1 to 5 V
V
oltage input
20
0 to 5 V
21
0 to 10 V
 Output Assignments
Thirteen
 output functions are available. Allocate these functions to
the
 control outputs 1 and 2 and auxiliary outputs 1 and 2.
There are some limitations on some output function allocations.
Output
 function types and allocation
 limitations are as described in
the
 following.
Identical
 output functions cannot be
 allocated doubly to the control
output
 1 or 2 and auxiliary output 1 or 2.
Standard Models
Assignment
 
Destination
Control Output Auxiliary Output
Output Function
1 2 1 2
Control output (heat)
(see note 1)
Yes Yes No No
Control output (cool)
(see note 1)
Yes Yes No No
Alarm 1
Yes Yes Yes Yes
Alarm 2
Yes Yes Yes Yes
Alarm 3
Yes Yes Yes Yes
HBA (see notes 1, 2)
Yes Yes Yes Yes
LBA (see note 1)
Yes Yes Yes Yes
T
ime signal 1
Yes Yes Yes Yes
T
ime signal 2
Yes Yes Yes Yes
Program end
Yes Yes Yes Yes
Stage output 
(see note 1)
Yes Yes Yes Yes
Error 1 : Input error
No No Yes Yes
Error 2 : A/D convertor
error
No No Yes Yes
Note: 1. Assignment
 is not possible with the control valve control
type.
2. Heater
 burnout alarm is not available for the E5CK.
Position-proportional Models
Position-proportional-type Controllers support nine output func-
tions.
 These are assigned to auxiliary outputs 1 and 2.
Restrictions
 on assignment destinations are placed on
 some of the
outputs.
 The following table shows where outputs may be assigned
to.
Assignment
 
Destination
Control Output Auxiliary Output
Output Function
1 2 1 2
Alarm 1
No No Yes Yes
Alarm 2
No No Yes Yes
Alarm 3
No No Yes Yes
T
ime signal 1
No No Yes Yes
T
ime signal 2
No No Yes Yes
Stage output
No No Yes Yes
Program end output
No No Yes Yes
Error 1 : Input error
No No Yes Yes
Error 2 : A/D converter
error
No No Yes Yes
With control output (cool), the conditions for switching from stan-
dard control to heating and cooling control are reached when the
output function is assigned at the cooling side during heating and
cooling
 control.
In
 other words, heating and
 cooling control is carried out when con
-
trol output (cool) is assigned, and standard control is carried out
when
 output is not assigned.