Alarm Type
Alarms 1 and 2
Note: 1. With set values 1, 4 and 5, the upper and lower limit values
can be set independently for each alarm type and are
expressed as "L" and "H."
2. Set value: 1, Upper- and lower-limit alarm
3. Set value: 4, Upper- and lower-limit range
4. Set value: 5, Upper- and lower-limit with standby sequence
For upper- and lower-limit alarms in the above diagrams, the
alarm is always OFF
in cases 1 and 2 if the hysteresis for
the upper and lower limits overlaps, and the alarm is always
OFF for case 3.
5. Set value: 5, Upper- and lower-limit with standby sequence
alarm.
Alarm is always OFF
when the upper-limit and lower-limit
hysteresis overlaps.
6. Refer to Alarm Hysteresis for information on standby
sequences.
Alarm 3
Note: If the alarm type is set to value from 1 to 7, set the alarm value
as the deviation from the SP.
Use host communications or the E5ZN-SDL Setting Display Unit to
set the alarm type separately for each alarm for alarms 1 to 3. The
default settings are for an upper-limit alarm (set value: 2). Set the
alarms separately for each channel.
Set
value
Alarm type Alarm output
When alarm value X is
positive
When alarm value X is
negative
0 No alarm Output OFF
1 Upper and
lower limits
(See note 1.)
(See note 2.)
2 Upper limit
3 Lower limit
4 Upper and
lower limits of
range (See
note 1.)
(See note 3.)
5 Upper- and
lower-limit
alarm with
standby se-
quence (See
notes 1 and 6.)
(See note 5.)
(See note 4.)
6 Upper-limit
alarm with
standby se-
quence (See
note 6.)
7 Lower-limit
alarm with
standby se-
quence
8 Absolute-val-
ue upper limit
9 Absolute-val-
ue lower limit
10 Absolute-val-
ue upper limit
with standby
sequence
(See note 6.)
11 Absolute-val-
ue lower limit
with standby
sequence
(See note 6.)
L
ON
OFF
H
SP
ON
OFF
X
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
SP
L
ON
OFF
H
SP
L
ON
OFF
H
SP
ON
OFF
X
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
SP
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
LHSP LHSP LHSP
LHSP
SPLH
Case 1 Case 2 Case 3 (Always ON)
H < 0, L < 0
H < 0, L > 0
H < L
H > 0, L < 0
H > L
H < 0, L > 0
H L
H > 0, L < 0
H L
L
HSP
LHSP LHSP
LHSP
LHSP
Case 1 Case 2 Case 3 (Always ON)
H < 0, L < 0
H < 0, L > 0 H > 0, L < 0
H < 0, L > 0
H L
H > 0, L < 0
H L
Set
value
Alarm type Alarm output
When alarm value X is
positive
When alarm value X is
negative
0 No alarm Output OFF
1 Upper and
lower limits
Always ON
2 Upper limit
3Lower limit
4 Upper and
lower limits of
range
Always OFF
5 Upper- and
lower-limit
alarm with
standby se-
quence
Always OFF
6 Upper-limit
alarm with
standby se-
quence
7 Lower-limit
alarm with
standby se-
quence
8 Absolute-val-
ue upper limit
9 Absolute-val-
ue lower limit
10 Absolute-val-
ue upper limit
with standby
sequence
11 Absolute-val-
ue lower limit
with standby
sequence
X
ON
OFF
X
SP
ON
OFF
X
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
X
SP
X
ON
OFF
X
SP
ON
OFF
X
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
SP
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0

Other manuals for Omron E5ZN Series