H3DS-G
H3DS-G
22
Specifications
General
Item H3DS-G
Operating
mode
Star-delta operation
Operating/Reset method
T
ime-limit operation/Self-reset
External connections
Screw terminal, screwless spring terminal
T
erminal block
Screw terminal type:
Clamps two 2.5-mm
2
max. bar terminals without sleeves.
Screwless spring terminal type:
Clamps two 1.5-mm
2
max. bar terminals without sleeves.
T
erminal screw tightening
torque
0.98 N
S
m max.
Output type
(Star operation circuit) Relay: SPST
-NO
(Delta operation circuit) Relay: SPST
-NO
Mounting method
DIN track mounting (see note)
Attachment
Nameplate label
Approved standards
UL508, CSA C22.2 No.14
Conforms to EN61812-1, IEC60664-1 (VDE01
10) 4 kV/2, VDE0106/P100
Output category according to IEC60947-5-1 (AC-13; 250 V 5A/AC-15; 250 V 1 A/DC-13; 30 V 0.1 A)
Note:
Can be mounted to 35-mm DIN T
rack with a plate thickness of 1 to 2.5 mm.
Time Ranges
Time
scale
Star operation time ranges
x 1
1 to 12 s
x 10
10 to 120 s
Star-delta transfer time
Programmable at 0.05 s, 0.1 s, 0.5 s, or 1 s
Ratings
Rated
supply voltage (see note)
24 to 230 V
AC (50/60 Hz)/24 to 48 VDC
Operating voltage range
85% to 1
10% of rated supply voltage
Power reset
Minimum power-off time: 0.5 s
Reset voltage
2.4 V
AC/DC max.
Power consumption
AC:
21 V
A max./1.7 W max. (typical: 20 V
A/1.6 W) at 230 V
AC
1
1 V
A max./2.0 W max. (typical: 8.6 V
A/1.5 W) at 100 to 120 V
AC
DC:
1.3 W max. (typical: 1.2 W) at 24 VDC
0.7 W max. (typical: 0.6 W) at 48 VDC
Control output
Contact output:
5 A at 250 V
AC with resistive load (cosφ
= 1)
5 A at 30 VDC with resistive load (cos
φ
= 1)
Ambient temperature
Operating: –10°
C to 55
°
C (with no icing)
Storage: –25°
C to 65
°
C (with no icing)
Ambient humidity
Operating:
35% to 85%
Note:
DC ripple rate: 20% max.