2222
H5CC
Timer
Mode b-5: One-shot flicker (Timer resets when power comes ON.)
Basic operation Detailed operation
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The control output is turned ON when time is up. It
resets in one cycle
.
While the start signal is ON, the timer starts when the
po
we
r comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the se
t time is too short. Set the value to at least
100 ms (contact output type).
Mode C: Signal ON/OFF delay I (Timer resets when power comes ON.)
Basic operation Detailed operation
* Start signal input is enabled during timing.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
The timer resets when the time is up.
Note: O
utput is disabled when the setting is 0.
Mode d: Signal OFF delay I (Timer resets when power comes ON.)
Basic operation Detailed operation
* Start signal input is enabled during timing.
The control output is ON when the start signal is ON
(except when the power is OFF or the reset is ON).
The timer resets when the time is up.
Note: Output functions only during start signal input
when
setting is 0.
Mode E: Interval (Timer resets when power comes ON.)
Basic operation Detailed operation
* Start signal input is enabled during timing.
Timing starts when the start signal comes ON.
The timer resets when the time is up.
While the start signal is ON, the timer starts when the
powe
r comes ON or when the reset input goes OFF.
Note: O
utput is disabled when the setting is 0.
Output
*
Start signal
input
Timing
Power
Timing
0
UP
DOWN
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
Output
*
Start signal
input
Timing Timing
Power
0
UP
DOWN
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
Output
*
Start signal
input
Timing
Power
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
*
Start signal
input
Timing
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram