H5CC
88
Applicable Standards
*1. The following safety standards apply to models with sockets (H5CC-L8@/-A11@).
cUL (Listing): Applicable when an OMRON P2CF(-E) Socket is used.
cUR (Recognition): Applicable when any other socket is used.
*2. C
CC certification requirements
I/O Functions
For details, refer to the timing charts on page 20, page 31, and page 36.
*1. The H5CC-L8E@ does not have an input.
*2. The H5CC-L@ does n
ot have a gate input.
*3. For the H5CC-AWSD.
Response Delay Time When Resetting (Transistor Output)
The following table shows the output delay time from when the reset signal is input until the output is turned OFF.
(Reference value)
Approved safety standards
cULus (or cURus): UL508/CSA C22.2 No. 14 *1
Conforms to EN61812-1: Pollution degree 2/overvoltage category III
B300 PILOT DUTY, 1/4 HP 120 VAC, 1/3 HP, 240 VAC, 5 A, 250 VAC/30 VDC resistive load
VDE0106/P100
CCC: GB/T 14048.5 Pollution degree 2/overvoltage category III *2
RCM
UKCA
EMC
(EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: EN61000-4-2: 4 kV contact discharge
8 kV air discharge
Immunity RF-interference: EN61000-4-3: 10 V/m (Amplitude modulated, 80 MHz to 1 GHz);
3 V/m (Amplitude modulated, 1.4 G to 2 GHz);
1 V/m (Amplitude modulated, 2 G to 2.7 GHz);
10 V/m (Pulse-modulated, 900 MHz±5 MHz)
Immunity Conducted Disturbance: EN61000-4-6: 10 V (0.15 to 80 MHz)
Immunity Burst: EN61000-4-4: 2 kV power-line;
1 kV I/O signal-line
Immunity Surge: EN61000-4-5: 1 kV line to lines (powe
r and out
put lines (relay outputs));
2 kV line to ground (power and output lines (relay outputs))
Immunity Voltage Dip/Interruption: EN61000-4-11: Voltage Dip
1 cycle, 100% (rated voltage)
10/12 cycle, 60% (rated voltage)
25/30 cycle, 30% (rated voltage)
Interruption
250/300 cycle, 100% (rated voltage)
Rated operating voltage Ue
Rated operating current Ie
Contact output:
AC-15: Ue: 250 VAC, Ie: 3 A
AC-13: Ue: 250 VAC, Ie: 5 A
DC-13: Ue: 30 VDC, Ie: 0.5 A
Transistor output:
DC-13: Ue: 30 VDC, Ie: 0.1 A
Rated insulation voltage 250 V
Rated impulse withstand voltage
(altitude: 2,000 m max.)
4 kV (at 240 VAC)
Conditional short-circuit current 1000 A
Inputs *1
Start signal
Normally functions to start timing.
In modes A-2 and A-3, disable timing. In mode S, starts and stops timing.
Reset
• Resets present value. (In elapsed time mode, the present value returns to 0; in remaining time
mode, the present value retur
ns to the set value.)
• Count inputs are not accepted and control output turns OFF while reset input is ON.
• Reset indicator is lit while reset input is ON.
Gate *2 Disables timing. (If a reset occurs while the gate input is ON, a reset will be performed.)
Outputs
Control output (OUT)
Outputs take place according to designated operating mode when timer reaches corresponding set
value.
Forecast value
setting *3
Control output (OUT2) Turns ON when the present value reaches the set value.
Forecast output (OUT1) Turns ON when the present value reaches the forecast value.
Absolute value
setting *3
Control output 2 (OUT2) Turns ON when the present value reaches the set value 2.
Control output 1 (OUT1) Turns ON when the present value reaches the set value 1.
Minimum reset signal width Output delay time
1 ms 0.58 to 0.78 ms
20 ms 13.7 to 17.2 ms