Characteristics
* Refer to Electrical Life Test Curve.
Electrical Life Test Curve (Reference Values)
Accuracy of operating time and setting error
(including temperature and voltage
influences)
Po
wer-ON start: ±0.01%±0.05 s max. *1
Signal start: ±0.005%±0.03 s max. *1
Signal start for transistor output model: ±0.005%±3 ms max. *1 *2
If the set value is within the sensor waiting time at sta
rtup the control output of the H5CC will not turn ON until the
sensor waiting time passes.
*1. The va
lues are based on
the set value.
*2. The value is applied for a minimum input signal width of 1 ms.
Insulation resistance
100 MΩ min. (at 500 VDC)
between current-carrying terminal and exposed non-current-carrying metal parts, between non-continuous contacts
Dielectric strength
2,900 VAC, 50/60 Hz for 1 min between current-carrying terminal and operating section
2,000 VAC, 50/60 Hz for 1 min between power supply an
d input circuits
for models other than the H5CC-A11F and H5CC-L8E@
(1,500 VAC for 12 to 48 VDC/24 VAC)
1,500 VAC, 50/60 Hz for 1 min between control output, power supply,
and inpu
t circuits
(for models other than the H5CC-L8E@) for H5CC
-@SD
2,000 VAC, 50/60 Hz for 1 min between control output, power supply,
and input circuits (for models other than the H5CC-L8E@) fo
r othe
r models
1,000 VAC, 50/60 Hz for 1 min between non-continuous contacts
Impulse withstand voltage
5 kV (between power terminals) for 100 to 240 VAC, 1.0 kV for 24 VAC/12 to 48 VDC
7.4 kV (between current-carrying terminal and operating section)
Static immunity
Malfunction: 8 kV
Destruction: 15 kV
Vibration resistance
Destruction 10 to 55 Hz with 0.75-mm single amplitude each in three directions for 2 h each
Malfunction 10 to 55 Hz with 0.35-mm single amplitude each in three directions for 10 min each
Shock resistance
Destruction 300 m/s
2
in three directions, three cycles
Malfunction 100 m/s
2
in three directions, three cycles
Life expectancy
Mechanical
10,000,000 operations min.
(under no load at switching frequency of 1,800 operations/h and ambient temperature of 23°C)
Electrical
100,000 operations min.
(5 A at 250 VAC, resistive load at 1,800 operations/h and ambient temperature of 23°C) *
Weight Approx. 115 g (Timer only)
30 VDC L/R = 7 ms
250 VAC/30 VDC
cosI = 1
250 VAC cosI = 0.4
0 1 2 3 4 5
1,000
500
100
50
10
Switching operations (× 10
4
)
Load current (A)
A maximum current of 0.15 A can be switched at 125 VDC (cosφ =1)
and a maximum current of 0.1 A can be switched if L/R is 7 ms.
In both cases, a life of 100,000 operations can be expected.