Multifunction Digital Timer H5CX-A/-L (Timer Function) 21
Operation in Run Mode
Present Value and Set Value
These items are displayed when the power is turned ON. The
present value is displayed in the main display and the set value is
displayed in the sub-display. The values displayed will be determined
by the settings made for the time range and the timer mode in func-
tion setting mode.
Present Value and ON Duty Ratio (Output Mode = Z)
The present value is displayed in the main display and the ON duty
ratio is displayed in the sub-display. “SET1” lights at the same time.
Set the ON duty ratio used in ON/OFF-duty adjustable flicker mode
(Z) as a percentage.
If a cycle time is set, cyclic control can be performed in ON/OFF-duty
adjustable flicker mode simply by changing the ON duty ratio.
The output accuracy will vary with the time range, even if the ON
duty ratio setting is the same. Therefore, if fine output time adjust-
ment is required, it is recommended that the time range for the cycle
time is set as small as possible.
Examples:
1. If the cycle time is 20 s, the ON duty ratio is 31%, and the time
range is 1 s to 9999 s, the ON time is given by the following:
20 (s)
´ = 6.2 (s) ® Rounded off to the nearest integer
(because of the time range setting)
® ON time = 6 s
2. If the cycle time is 20.00 s, the ON duty ratio is 31%, and the time
range is 0.01 s to 99.99 s, the ON time is given by the following:
20.00 (s)
´ = 6.200 (s) ® Rounded off to 2 decimal places
(because of the time range setting)
® ON time = 6.20 s
Present Value and Cycle Time (Output Mode = Z)
The present value is displayed in the main display and the cycle time
is displayed in the sub-display. “SET2” lights at the same time.
Set the cycle time used in ON/OFF-duty adjustable flicker mode (Z).
When Output Mode Is Not Z
Present value
Set value
Set each digit for the set value using the corresponding keys.
Present value
ON duty ratio
Cycle time
When Output Mode Z Is Selected
Present value
Set each digit for the cycle time using the corresponding keys.
Set each digit for the ON duty ratio using the corresponding keys.
(The keys for the 4th digit cannot be used.)
100
ON time = Cycle time ×
ON duty ratio (%)
100
31 (%)
100
31 (%)
Elapsed cycle time
ON duty set as a percentage
Cycle time
ON duty (%)
Output control
Close Open
Opening/closing valve
Fully closedFully open
0%100%
ON duty
Up/down keys used for analog
adjustment of the ON duty

Other manuals for Omron H5CX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron H5CX and is the answer not in the manual?

Omron H5CX Specifications

General IconGeneral
Time Range0.001 s to 9999 h
Mounting MethodFlush mounting
Output TypeRelay or Transistor
Control OutputRelay or Transistor
Operating Temperature-10 to 55°C
Storage Temperature-25 to 65°C
Input TypeNPN or PNP
Power Supply Voltage24V AC/DC, 100-240V AC
Operating Voltage Range85% to 110% of rated voltage
Operating ModesON-delay, One-shot, Interval
Contact Rating5 A at 250 VAC
MountingPanel
Dimensions48 x 48 mm
Protection StructureIP66 (front panel)