Page #52 background imageLoading...
Page #52 background image
2-7
List of Settings Section 2
List of
Settings
Display Adjustment Level
Note The values beginning with H’ in the Monitor/Setting range column are used when setting or monitoring
data via communications.
Comparative Set Value Level
Variable
type
Address Parameter
name
Character Monitor/Setting range Character Default
setting
Decimal
point
Unit Model
XVSH
C6 0000 Compara-
tive set
value dis-
play
sv.dsp H’00000000: OFF(0),
H’00000001: ON(1)
off, on off --- ---
0001 Display
refresh
period
d.ref H’00000000: OFF(0),
H’00000001: 0.5 s(1),
H’00000002: 1 s(2),
H’00000003: 2 s(3),
H’00000004: 4 s(4)
off, 0
. 5, 1,
2, 4
off --- s
0002 Display
color selec-
tion
color H’00000000: Green
(red)(0), H’00000001:
green(1), H’00000002:
red (green)(2),
H’00000003: red(3)
grn-r, grn,
red-g, red
grn-r --- ---
0003 Display
value selec-
tion
disp H’00000000: PV(0),
H’00000001: MAX(1),
H’00000002: MIN (2)
pv, max, min pv --- ---
0004 Automatic
display
return
ret H’00000000 to
H’00000063: (0 to 99)
0 to 99 10 --- s
0005 Position
meter type
pos-t H’00000000: OFF(0),
H’00000001: increase(1),
H’00000002: increase
(inverted)(2),
H’00000003: deviation
(3),
H’00000004: deviation,
(inverted)(4)
off, inc,
inc-r, dev,
dev-r
inc --- ---
0006 Position
meter upper
limit
pos-h H’FFFFB1E1 to
H’0001869F
(
19,999 to 99,999)
:9999 to
99999
X (VD):
19999
X (AD):
19999
X (VA):
4000
X (AA):
10000
V: 19999
S: 99999
H: 1300
. 0
According to
the decimal
position set-
ting
---
0007 Position
meter lower
limit
pos-l H’FFFFB1E1 to
H’0001869F
(
19,999 to 99,999)
:9999 to
99999
X (VD):
:9999
X (AD):
:9999
X (VA): 0
X (AA): 0
V: 0
S: :9999
H: -200
. 0
According to
the decimal
position set-
ting
---
0008 PV decimal
point indica-
tion
pvdp H’00000000: OFF(0)
H’00000001: ON(1)
off, on on --- --- x x x
Variable
type
Address Parameter
name
Character Monitor/Setting range Character Default
setting
Decimal
point
Unit Model
XVSH
C8
0000 Compara-
tive set
value 0 HH
sv0.hh H’FFFFB1E1 to
H’0001869F
(
19,999 to 99,999)
:9999 to
99999
99999 According to
the decimal
position set-
ting
---
0001 Compara-
tive set
value 0 H
sv0.h H’FFFFB1E1 to
H’0001869F
(
19,999 to 99,999)
:9999 to
99999
99999 According to
the decimal
position set-
ting
---
0002 Compara-
tive set
value 0 L
sv0.l H’FFFFB1E1 to
H’0001869F
(
19,999 to 99,999)
:9999 to
99999
:9999 According to
the decimal
position set-
ting
---
0003 Compara-
tive set
value 0 LL
sv0.ll H’FFFFB1E1 to
H’0001869F
(
19,999 to 99,999)
:9999 to
99999
:9999 According to
the decimal
position set-
ting
---

Table of Contents

Other manuals for Omron K3HB-R

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron K3HB-R and is the answer not in the manual?

Omron K3HB-R Specifications

General IconGeneral
BrandOmron
ModelK3HB-R
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals