3 Error Tables
3-72
NJ-series Troubleshooting Manual (W503)
84200000 hex Link OFF
Error
A Link OFF state
occurred.
The Ethernet cable is broken
between the master and slaves.
The Ethernet cable connector is
disconnected.
The Ethernet cable is not con-
nected.
S NJ-series
CPU Unit
Built-in Ether-
CAT Port
User’s Manual
(Cat. No.
W505)
24200000 hex Slave Node
Address
Duplicated
The same slave
address is used for
two nodes.
The same node address is set
for more than one slave.
S Same as
above.
34400000 hex Network
Configura-
tion Informa-
tion Error
There is an error in
the network config-
uration information.
The power supply to the Con-
troller was interrupted or com-
munications with the Sysmac
Studio were disconnected while
downloading the network con-
figuration information.
S Same as
above.
50010000 hex
(Ver. 1.02)
Controller
Insufficient
Memory
Warning
The amount of data
for the EtherCAT
slave configuration,
network-published
information, or
other data exceeds
the value that is
specified for the
CPU Unit. You may
not be able to per-
form online editing
or other operations.
The amount of data for the
EtherCAT slave configuration,
network-published information,
or other data exceeds the value
that is specified for the CPU
Unit.
S Same as
above.
84210000 hex Network
Configura-
tion Error
The EtherCAT net-
work configuration
is incorrect.
Slave output ports are con-
nected to each other.
The master and slave are con-
nected with the slave output
port.
The number of connected
slaves exceeded the maximum
number of slaves, 192 nodes,
for the EtherCAT master.
S Same as
above.
84220000 hex Network
Configura-
tion Verifica-
tion Error
A slave that is in the
network configura-
tion information is
not connected. Or,
a slave that is not in
the network config-
uration information
is connected.
A slave that is in the network
configuration information is not
connected.
There is a node address mis-
match.
A different slave from the one
tha
t is specified in the network
configuration information is
connected.
A slave that is not in the net-
work configuration information
is connected.
The Ethernet physical layer is
broken between two slaves.
S Same as
above.
84230000 hex Slave Initial-
ization Error
Slave initialization
failed.
An error occurred in EtherCAT
master processing.
An initialization error occurred
in the EtherCAT slave.
S Same as
above.
84280000 hex Slave Appli-
cation Error
An error occurred in
the slave applica-
tion.
An error was detected in the
slave’s application layer status
register.
S Same as
above.
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info