3-73
3 Error Tables
NJ-series Troubleshooting Manual (W503)
3-1 Errors by Source
3
3-1-5 Errors in the EtherCAT Master Function Module
84290000 hex Process Data
Transmis-
sion Error
Sending process
data failed.
It was not possible to send the
EtherCAT frame during the
EtherCAT communications
period.
The frame transmission jitter
exceeded the limit.
S NJ-series
CPU Unit
Built-in Ether-
CAT Port
User’s Manual
(Cat. No.
W505)
842B0000 hex Process Data
Reception
Timeout
Process data
reception timed out.
The Ethernet cable is broken.
The Ethernet cable for Ether-
CAT is disconnected.
A general-purpose Ethernet
hub is connected.
The master failed.
The slave failed.
The Ethernet cable is too long.
The CPU Unit task period is too
short.
Noise
S Same as
above.
842C0000 hex Process Data
Communica-
tions Error
An error occurred in
process data com-
munications.
A slave left the network even
though the disconnection oper-
ation was not performed.
Noise
The slave failed.
S Same as
above.
102F0000 hex
(Ver. 1.03)
EtherCAT
Slave Backup
Failed
The backup opera-
tion for an Ether-
CAT slave ended in
an error.
There is no connection
between the EtherCAT master
and the slave (Link OFF).
An error caused an incorrect
EtherCAT master status.
The EtherCAT network configu-
ration information does not
agree with the physical net-
work configuration.
The request to the EtherCAT
slave failed.
The EtherCAT master was tem-
porarily unable to perform the
processing because it was exe-
cuting other processing.
Initialization of the EtherCAT
slave failed.
It was not possible to read the
backup parameters from the
EtherCAT slave.
S Same as
above.
Event code Event name Meaning Assumed cause
Level
Reference
Maj Prt Min Obs Info