What to do if a specific output does not turn ON and the operation indicator does not light on Omron Control Unit?
- LLisa OlsenSep 8, 2025
If a specific output on your Omron Control Unit does not turn ON and the operation indicator does not light, check the following: * Correct the user program to make a longer output ON time if the output ON time is too short. * Correct the user program so that only one Out instruction controls the output bit if the output bit is used in more than one Out instruction. * Replace the Output Unit if there are faulty output circuits.