NJ-series CPU Unit Hardware User’s Manual (W500)
5-2  Troubleshooting
5
5-2-4  Error Descriptions
* For details, refer to I/O Operation for Major Fault Level Controller Errors on page 5-6.
Event name Non-volatile Memory Data Corrupted Event code 1002 0000  hex
Meaning A file that must be in non-volatile memory is missing or corrupted.
Source PLC Function Module Source details None Detection 
timing
At power ON or 
Controller reset
Error attributes Level Major fault Recovery Cycle the power 
supply or reset 
the Controller.
Log category System
Effects User program Stops. Operation Stops.*
System-defined 
variables
Variable Data type Name
None --- ---
Cause and 
correction
Assumed cause Correction Prevention
The Controller power supply was 
turned OFF while the BUSY indicator 
was lit.
Clear all of memory and then down-
load the project from the Sysmac Stu-
dio.
Do not turn OFF the power supply 
while the BUSY indicator is lit.
The power supply to the Controller 
was interrupted momentarily while the 
BUSY indicator was lit.
Take appropriate measures to ensure 
that the specified power with the rated 
voltage and frequency is supplied in 
places where the power supply is 
unstable.
The CPU Unit has failed. If this error remains even after making 
the above corrections, replace the 
CPU Unit.
None
Attached 
information
None
Precautions/
Remarks
None