3-7
3 Configuration Units
NJ-series CPU Unit Hardware User’s Manual (W500)
3-1 CPU Units
3
3-1-2 Components and Functions
Built-in EtherNet/IP Port (Port 1) Indicators
Indicator Color Status Contents
NET RUN Green Lit Normal startup status.
Flashing Ethernet communications are in progress.
Tag data link connection establishment in progress.
IP address acquisition with BOOTP in progress.
Not lit You cannot perform Ethernet communications.
The power supply is OFF or the CPU Unit was reset.
A MAC address error or communications Controller error
occurred.
NET ERR Red Lit An error for which the user cannot recover operation occurred.
A MAC address error or communications Controller error
occurred.
Flashing An error for which the user can recover operation occurred.
An error occurred in TCP/IP communications or CIP communi-
cations.
FTP server setting error, NTP server setting error, etc.
Tag data link setting error, tag data link verification error, etc.
Not lit There are no Ethernet communications errors.
The power supply is OFF or the CPU Unit was reset.
LINK/ACT Yellow Lit The link was established.
Flashing The link is established, and data communications are in progress.
Not lit A link was not established.
The cable is not connected.
The power supply is OFF or the CPU Unit was reset.