6 Digital Input Units
6 - 20
NX-series Digital I/O Unit User’s Manual (W521)
4 Click the Transfer to Unit Button.
The settings are transferred from the Sysmac Studio to the NX Unit.
The settings are reflected after the Unit is restarted.
The Unit is required to restart after the transfer of Unit operation settings on the Sysmac Studio
is completed. Always sufficiently check the safety at the connected devices before you transfer
the Unit operation settings.
Note that when you use this function, the time for which the input value actually turns ON or turns OFF
is delayed from the initial input to the input terminals until ON delay time or OFF delay time in the follow-
ing table.
Precautions
Delay time Description
ON delay time ON response time + input filter time
OFF delay time OFF response time + input filter time