7 Troubleshooting
7-13
NJ/NX-series Database Connection CPU Units User’s Manual (W527)
7
7-2 Troubleshooting
7-2-1 Error Table
Event code Event name Meaning Assumed cause
Level
Reference
Maj
Prt
Min
Obs
Info
54013010hex Log Code Out
of Range
The value of the
entered log code
is outside the
valid range.
ï‚– A value outside the valid range
from 0 to 9999 was specified.
S
7-35
54013011hex DB
Connection
Disconnected
Error Status
The instruction
could not be
executed
because the DB
Connection had
been
disconnected
due to an error.
ï‚– The power supply to the server
is OFF.
ï‚– The DB is stopped in the
server.
ï‚– The Ethernet cable connector
is disconnected.
ï‚– The Ethernet cable is broken.
ï‚– Noise
S
7-35
54013012hex DB
Connection
Instruction
Execution
Timeout
The instruction
was not
completed within
the time
specified for
timeout.
ï‚– The power supply to the server
is OFF.
ï‚– The Ethernet cable connector
is disconnected.
ï‚– The Ethernet cable is broken.
 The server’s processing time is
long.
S
7-36
54013013hex DB
Connection
Service Error
Stop
The instruction
could not be
executed
because the DB
Connection
Service was
stopped due to
an error.
ï‚– The DB Connection settings
are corrupted.
S
7-36
54013014hex Data Already
Spooled
One or more
SQL statements
are already
stored in the
Spool memory.
ï‚– A DB_Insert or DB_Update
instruction was executed when
one or more SQL statements
were already stored in the
Spool memory.
ï‚– A DB_Select or DB_Delete
instruction was executed when
one or more SQL statements
were already stored in the
Spool memory.
S
7-37
54013015hex DB
Connection
Service
Initializing
The instruction
could not be
executed
because the
initialization
processing of
the DB
Connection
Service is in
progress.
ï‚– The relevant instruction was
executed during the
initialization processing of the
DB Connection Service.
S
7-37
54013016hex DB in Process The instruction
could not be
executed
because the DB
is under
processing in the
server.
ï‚– Though a DB Connection
Instruction Execution Timeout
occurred for the previous
instruction, the relevant
instruction was executed
before completion of the DB’s
processing in the server.
S
7-38