7 Troubleshooting
7-30
NJ/NX-series Database Connection CPU Units User’s Manual (W527)
Event name
Unregistered DB Map Variable
Event code
5401300Ahex
Meaning
The specified DB Map Variable has not been registered.
Source PLC Function Module Source details Instruction Detection
timing
At instruction
execution
Error attributes
Level
Observation
Recovery
---
Log category
System
Effects
User program
Continues. Operation The relevant instruction will end according to
specifications.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The DB Map Variable has not
been created by a
DB_CreateMapping instruction.
Correct the user program so that
the relevant instruction is executed
after the DB Map Variable is
created by a DB_CreateMapping
instruction.
Write the user program so that the
relevant instruction is executed
after the DB Map Variable is
created by a DB_CreateMapping
instruction.
A variable that is not registered
as a DB Map Variable was
specified in MapVar.
Check the input parameters of the
relevant instruction and correct the
user program.
In the input parameters of the
relevant instruction, specify the DB
Connection specified in the
DB_CreateMapping instruction and
the DB Map Variable created by
the DB_CreateMapping instruction.
The DB Connection specified in
the relevant instruction is
different from the one specified
at the execution of
DB_CreateMapping instruction.
Attached
information
Attached information 1: Error Location
Attached information 2: Error Location Detail, Rung Number. For a program section, the rung number from the
start of the section is given. For ST, the line number is given.
Attached information 3: Instruction Name and Instruction Instance Name Where Error Occurred. If there is
more than one instruction, all of them are given. If the instruction cannot be identified, nothing is given.
Attached information 4: Expansion Error Code (ErrorIDEx)
Precautions/
Remarks
None

Table of Contents