EasyManua.ls Logo

Omron Powli BY35S - Page 36

Omron Powli BY35S
63 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BY35S / BY50S / BY80S / BY120S
4
25
2. UPS operation mode settings
2-1 Settable items and explanations
There are 2 items to select.
1) Cold start ON/OFF setting
2) Input power sensitivity setting
The settings available for this operation are shown below.
1) Cold start ON/OFF setting
• Cold start OFF mode
The unit can start up only when there is AC input.
• Cold start ON mode
It is possible to start up the unit even when there is no AC input plug.
Normal operation occurs when AC input is ON. The output frequency is the same as the fre-
quency the last time there was AC input.
• When using the cold start function
When performing operation with cold start a second time, turn OFF the power switch and wait
at least 20 seconds before turning it back ON.
If the time is too short, UPS may not start up.
2) Input power sensitivity setting
Two types of input sensitivity can be set.
• Standard voltage sensitivity mode
The power failure detection voltage is set to the standard setting. (Factory setting)
• High voltage sensitivity
The power failure detection voltage range is narrower than that at the standard setting.
The allowable voltage ranges for each setting are shown below.
Standard voltage sensitivity 86±3 to 114±3 VAC
High voltage sensitivity 95±3 to 108±3 VAC

Related product manuals