EasyManua.ls Logo

Omron Powli BY35S - Page 37

Omron Powli BY35S
63 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.UPS functions
26
The UPS operation mode can be set if the power switch is turned ON while the beeper stop /test
switch is pressed.
Note: While in setting mode, output from the power supply output is OFF even if the power
switch is ON.
Beeper stop/test
Power suppply ON/OFF
(1) When the beeper stop/test switch is briefl y pressed (for less than 1 second), the next item is
displayed.
Cold start ON/OFF setting
Input power sensitivity setting
(2) The unit enters the “individual item setting mode” when the beeper stop/test switch is
pressed and held (for more than 1 second).
(3) When the power switch is turned OFF, the setting mode quits and the unit enters power
switch OFF status (status
).
2-2 Settings
ON Cold start ON mode
C *1
C
D
D D
A B
OFF Cold start OFF mode (Factory-shipped setting)
C *1
C
D
D
D
*1 Displays the current setting value.
*2 The setting applied to BY35S/BY50S/BY80S/BY120S is the same as the standard voltage sensitivity setting.
D
Cold start
ON/OFF setting
Setting mode
Normal status
Input power
sensitivity setting
Standard voltage sensitivity setting (at shipment)
Low voltage sensitivity *2
High voltage sensitivity
There is AC input
Power switch “OFF” (Status No. 2)
B
C
D
A
Turn ON the power switch while the beep stop/test switch is pressed.
Turn OFF the power switch.
Press and hold the beep stop/test switch (for more than 3 seconds).
Press the beep stop/test switch (for less than 3 seconds).

Related product manuals