l
Functionswitchingsettingsofthebackuppowersupplystopsignal
By setting the jumper on the printed circuit board of the SC08G (jumper symbol: JP5), switch the stop
signal function as follows:
Jumper
symbol
Jumper
setting
(Factory setting)
Function
Jumper
setting
Jumper setting
JP5 BS side
The UPS stops upon receiving the
High signal input.
BS side
The UPS stops upon receiving the
Low signal input.
l
Highsignalinputvoltagerangesettingsofthebackuppowersupplystopsignal
By setting the jumper on the printed circuit board of the SC08G (jumper symbol: JP7), set the input volt-
age range on the High side of the backup power supply stop signal as follows:
Jumper
symbol
Jumper
setting
(Factory setting)
Function
Jumper
setting
Jumper setting
JP7
24 VDC
side
High signal input voltage range
from 8V to 24 V
12 VDC
side
High signal input voltage range from
5V to 12 V
Caution
Do not apply voltage higher than the set High signal input voltage range.
● Doing so may cause failure or damage of the card unit, resulting in a re or electric shock.
l
UPSStart/StopsettingoftheremoteON/OFFsignal
By setting the jumper on the printed circuit board of the SC08G (jumper symbol: JP7), set the UPS Start/
Stop by the remote ON/OFF signal as follows:
Jumper
symbol
Jumper
setting
(Factory setting)
Function
Jumper
setting
Jumper setting
JP6
OP-OFF
side
External contact open UPS stop
CL-OFF
side
External contact open UPS start
External contact close UPS start External contact close UPS stop