3.1 Precautions on Wiring
20
Noise Prevention
Example of Wiring for Noise Prevention
* 1. For the wires connected to the casings for installation purposes, use wires with a diameter of 3.5 mm
2
or larger. Flat braided copper wires are recommended.
* 2. Use twisted pair wires for section P.
Correct Grounding
Servomotor frame grounding:
Be sure to connect the FG grounding terminal on the frame of the servomotor to the grounding termi-
nal on the SERVOPACK.
Be sure to ground the grounding terminal of the SERVOPACK.
If the wires of the servomotor’s main circuit are laid in a metal conduit, ground the conduit and the
grounding box.
One-point grounding must be used.
M
(FG)
U
W
V
L2
L1
CN2
CN1
SERVOPACK
SJDE
Servomoto
r
Operation relay sequence
P
P
P
1LF
AVR
(Grounding)
*2.
Casing
Casing
Casing
*1.
*1.
Casing
Grounding plate
Groudning: Ground to one point only.
Min. grounding resistance: 100 Ω
2LF
Min. wire size
: 3.5 mm
2
Min. wire size
: 3.5 mm
2
Min. wire size
: 3.5 mm
2
Min. wire size: 3.5 mm
2
Min. wire size: 3.5 mm
2
2 mm
2
or larger
Casing
200 VAC
PG
Noise filter
*1.
User signal generating circuit