3.7 SERVOPACK Main Circuit Wire Size
28
3.7 SERVOPACK Main Circuit Wire Size
Cable Types
• Wire sizes are selected for three cables per bundle at 40 ° C ambient temperature with the rated cur-
rent.
• Use cables with a minimum withstand voltage of 600 V for main circuits.
• If cables are bundled in PVC or metal ducts, consider the reduction ratio of the allowable current.
• Use heat-resistant cables under high ambient or panel temperatures where normal vinyl cables will
rapidly deteriorate.
• Do not use cables under continuous regenerative state.
Wire Size and Allowable Current
The following table shows the wire size and allowable current for three cables. Use a cable whose spec-
ifications meet or are less than allowable current in the table.
• 600 V Heat-resistant Vinyl Cables (HIV)
Note: The values in the table are only for reference.
Power Supply Input Terminals (L1, L2), Motor Connection Terminals (U, V, W),
and Regenerative Unit Connection Terminals (+, -)
Note: Connectors are used for all wiring.
Ground Terminal ( )
Symbol Name Allowable Conductor Temperature
PVC
Normal vinyl cable
−
IV
600 V vinyl cable
60 ° C
HIV
Temperature-resistant vinyl cable
75 ° C
AWG
Size
Nominal Cross
Section Diameter
mm
2
Configuration
Number of
wires/mm
2
Conductive
Resistance
Ω/mm
2
Allowable Current at Ambient Temperature
A
30 ° C 40 ° C 50 ° C
20 0.5 19/0.18 39.5 6.6 5.6 4.5
- 0.75 30/0.18 26.0 8.8 7.0 5.5
18 0.9 37/0.18 24.4 9.0 7.7 6.0
16 1.25 50/0.18 15.6 12.0 11.0 8.5
14 2.0 7/0.6 9.53 23 20 16
Capacity
W
SERVOPACK Type Ter m i n al Symb ol
L1, L2 U, V, W +, -
100
SJDE-01APA-OY
HIV1.25 mm
2
HIV1.25mm
2
Wiring length:
20 m max.
HIV1.25mm
2
Wiring length:
0.5 m max.
200
SJDE-02APA-OY
400
SJDE-04APA-OY
HIV2.0 mm
2
750
SJDE-08APA-OY
Wire Size Term i n al S c re w S i ze Tightening Torque
HIV 2.0 mm
2
min.
M4 1.2 to 1.4Nxm